04/2022
-
Version 1
DoorTec Deutschland | www.doortec.online
13
Änderungen vorbehalten | Subject to Modifications
Remember to switch DIL switch 4 back to OFF posi-
tion
5.4 Reset to factory settings
Reset to factory settings by changing DIP switch 4
(S4) to ON position and push STOP and OPEN at the
same time within 2 seconds. The display will flash with
FACand program version number will be shown.
Parameter Value
Reverse time photo
xx = Reverse time of Photo in 1/100 seconds.
30 = 0.30 seconds
Range 0.05 – 0.99 sec.
This reverse time is also used as force reversing time.
(when using a single phase motor the parameter is to be set to 50 to avoid
problems with too fast reversing time)
Service counter setup
00 = No Service countdown
01 = 15 open cycles before service (for test only)
02 = 5000 open cycles before service
03 = 10000 open cycles before service
04 = 20000 open cycles before service
Reset for new countdown or selecting value:
Press STOP to select parameter value.
Press OPEN or CLOSE to select value.
Press STOP again minimum 2 sec.
CLR is shown 2 sec. in display to confirm new countdown.
Service count reaction
00 = Display shows E:04
01 = Switch to hold-to-run control and display shows E:04
If LED pad is mounted: Service LED will light when service countdown reach 0.
Delay time indication of miss-
ing encoder position
00 = 1 Sec.
01 = 2 Sec.
02 = 4 Sec.
Display shows E:09 after pre-set operation time without change of encoder
position. Failure can be reset by hold-to-run steps to find both end limits or re-
learning of limits.
03 = 4 Sec.
(After operation without change of encoder position the door will stop
and error code E:09 will be automatically reset)
Notice: No limit monitoring by selecting value 03.
Option relays K3
00 = K3 active when door is running
01 = K3 active when the door is closed
02 = K3 active when the door is open
Mechanical relay and terminals X17 needs to be mounted on the PCB on posi-
tion K3.