The Pressure Equipment Directive (PED) and the
Energy Performance of Buildings Directive (EPBD)
require a periodic inspection of heating applianc-
es in order to ensure a high degree of eciency
over a long term and, consequently, the least envi-
ronmental pollution.
It is necessary to replace safety-relevant com-
ponents after they have reached the end of
their useful life. This recommendation applies
only to heating appliances and not to indus-
trial heating processes. DUNGS recommends
replacing such components according to the
following table:
Safety relevant component USEFUL LIFE
DUNGS recommends
replacement after:
Operating EN
Standard
Valve proving systems 10 years 250.000 EN 1643
Pressure switch 10 years N/A EN 1854
Automatic burner control with ame safeguard 10 years 250.000 EN 298
Flame detector (UV probes) 10.000 h operating hours
Gas pressure regulators 15 years N/A
EN 88
EN 12078
Gas valve without valve testing system* 10 years
50.000-500.000
depends on diameter
EN 126
EN 161
Low gas pressure switch 10 years N/A IEN 1643
Pressure relief valve 10 years N/A
EN 88
EN 14382
Gas-air ratio control system 10 years N/A EN 12067
We reserve the right to make modications in the course of technical development.