EasyManua.ls Logo

dynatherm FP Series - Fp Series Boiler Specifications

dynatherm FP Series
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page | 9
FP SERIES BOILER SPECIFICATIONS
MODEL
FIRING
RATE
NET IBR
RATING
WATER
EFFICIENCY
STEADY STATE
HEAT
TRANSFER
SURFACE
DOMESTIC
HOT WATER
COIL GPM
STACK
TEMP
NO
GPH
MBH
SQ FT
COMB
AFUE
SQ FT
P1
P2
GR
NET
CO
2
FP18
0.65
71
484
89.1
87.3
19.0
5
1.8
290
230
13%
0.85
92
611
88.2
86.1
19.0
5
2.3
325
265
1.00
106
706
86.7
84.5
19.0
5
2.7
370
310
FP24
0.85
93
620
89.2
87.2
23.5
5
2.3
240
180
13%
1.00
108
720
88.1
85.9
23.5
5
2.7
275
215
1.25
132
880
86.5
83.9
23.5
5
3.3
350
290
FP36
1.25
139
927
90.5
88.5
32.5
6
3.4
260
200
13%
1.35
149
993
89.9
87.9
32.5
6
3.7
285
225
1.50
164
1093
89.0
87.0
32.5
6
4.1
325
265
FP48
1.65
167
1119
90.9
88.9
41.5
6
4.5
250
190
13%
2.00
182
1213
90.0
88.0
41.5
6
4.9
290
230
2.25
201
1340
88.8
86.8
41.5
6
5.3
320
26
* P1 is the coil capacity at 180°F, intermittent draw. Use these ratings to compare with boilers.
* P2 is the ability to heat water from 40°F to 140°F, without interruption, at the intended flow.
* DOE is the annual fuel use efficiency.
FLUE & FITTINGS
MODEL
“A”
“B”
“C”
WEIGHT
INSTALLATION CLEARNACE
FLUE
CHIMNEY
OUTLET
NO
LENGTH
WIDTH
HEIGHT
LBS
TOP
SIDE
FRONT
REAR
(DIA)
(MIN)
RETURN
FP18
36.5”
18.5”
35”
500
6”
12”
24”
20”
5”
6” RD
OR
6” SQ
1.25” NPT
OR
1.5” NPT
OR
2” NPT
FP24
42.5”
18.5”
35”
555
6”
12”
24”
26”
5”
FP36
54.5”
18.5”
35”
665
6”
12”
24”
38”
5”
FP48
66.5”
18.5”
35”
775
6”
12”
24”
50”
5”