3. The BAT-INV comms cable is from inverter comm port to master CAN IN port, BAT-BAT cable is
from master CAN OUT to slave1 CAN IN, slave1 CAN OUT to slave2 CAN IN…
4. Each pair of power cable, it’s limited continuous current is 150A, so if the inverter Max. work
current more than 150A, please add power cable according to the proportion.
3.2.4 Battery parameter settings on the inverter
Max Charging(Bulk) Voltage: 56.5V
Absorption Voltage: 56V
Float Voltage: 55.5V
Shut Down(cut off) Voltage: 48~50V
Shut Down(cut off) SOC: 20%
Restart Voltage: 52V
Max Charge Current: 50A*battery QTY
Max Discharge Current: 50A*battery QTY