Why does my E.L.B. F-350 Controller unit switch off automatically during normal operation?
- BBradley ChaneyAug 22, 2025
The unit might be switching off automatically due to several reasons: * The internal enclosure pressure is too near the limit. Try to readjust the leakage air nozzle. * The inlet pressure of the system fails briefly, possibly through activation of a large consumer. Increase the inlet pressure at the pressure regulator up to 3.5 bar maximum. * The pressure is below the MIN value because the enclosure has a leak. Seal off the enclosure and internal installations and possibly readjust the leakage air nozzle. * The pressure is below the MIN value because the cross-section of the inlet for compressed air/ inert gas is too small. Exchange hoses for ones with a larger diameter.