Operating Manual
System F-350
Documentation F-350
Version 2.99/04/2005
Sigrist Doku 10204E, Ver. 3

Table of Contents

Questions and Answers

  • C
    Caitlin StewartAug 22, 2025
    Why does my E.L.B. F-350 Controller unit switch off automatically during normal operation?
    • B
      Bradley ChaneyAug 22, 2025
      The unit might be switching off automatically due to several reasons: * The internal enclosure pressure is too near the limit. Try to readjust the leakage air nozzle. * The inlet pressure of the system fails briefly, possibly through activation of a large consumer. Increase the inlet pressure at the pressure regulator up to 3.5 bar maximum. * The pressure is below the MIN value because the enclosure has a leak. Seal off the enclosure and internal installations and possibly readjust the leakage air nozzle. * The pressure is below the MIN value because the cross-section of the inlet for compressed air/ inert gas is too small. Exchange hoses for ones with a larger diameter.
  • S
    Shannon FriedmanAug 25, 2025
    What to do if normal operation does not begin after a successful purge process with my E.L.B. F-350?
    • C
      camerongrahamAug 25, 2025
      If normal operation doesn't begin after a successful purge, it could be due to the following reasons: * The pressure is below the MIN value because the internal enclosure pressure is insufficient after the purge, and the pressure drops off. To resolve this, seal off the enclosure and internal installations and possibly readjust the leakage air nozzle. * The pressure is below the MIN value because the pressure regulator is incorrectly set (e.g., 2.0 bar static). Adjust the pressure regulator to, for example, 2.0 bar dynamic (i.e., for flow of compressed air/ inert gas).
  • B
    Brooke HernandezAug 26, 2025
    Why is the purge process aborted on my E.L.B. Controller?
    • D
      Dawn DeleonAug 26, 2025
      The purge process might be aborted if the air quantity is insufficient for a successful purge. Ensure that the dynamic inlet pressure isn't too low and set the inlet pressure to at least 2 bar dynamic.
  • C
    Corey SummersAug 27, 2025
    What happens when MAX pressure has been exceeded in E.L.B. F-350 Controller?
    • D
      Danielle NelsonAug 28, 2025
      If the maximum pressure has been exceeded, and the internal enclosure pressure is too high (possibly due to heat), readjust the leakage air nozzle.
  • A
    Amy ChavezAug 29, 2025
    Why does the display for enclosure pressure switch off after only 4 seconds on my E.L.B. F-350?
    • C
      Colton BakerAug 29, 2025
      The display might switch off after approximately 4 seconds if the pressure is below the MIN value, indicating that the internal enclosure pressure is insufficient after the purge and the pressure drops off. To solve this, seal off the enclosure and internal installations, and possibly readjust the leakage air nozzle.
  • D
    danieljacksonAug 31, 2025
    What does it mean if the display for enclosure pressure on my E.L.B. F-350 stays on longer than 4 seconds before switching off?
    • R
      Raymond StevensonSep 1, 2025
      If the display stays on longer than 4 seconds before switching off, it suggests that the pressure is below the MIN value. This indicates that the internal enclosure pressure is insufficient after the purge, and the pressure drops off. Seal off the enclosure and internal installations, and possibly readjust the leakage air nozzle.
  • T
    Travis WolfSep 2, 2025
    Why doesn't the display of enclosure pressure disappear 4 seconds after a pressure drop on my E.L.B. F-350?
    • T
      Timothy HicksSep 2, 2025
      If the display of enclosure pressure doesn't disappear 4 seconds after a pressure drop, it indicates that the “Switchpoint of Minimum Pressure“ is incorrectly set. Readjust the limit value.
  • S
    Scott PerezSep 4, 2025
    How to fix a defective remote control for E.L.B. Controller?
    • E
      Edward ColeSep 4, 2025
      If the remote control is defective, exchange it for a new one.
  • J
    Joshua MarshSep 6, 2025
    What to do for a Checksum error with a defective EPROM on E.L.B. F-350 Controller?
    • S
      Sandra JohnsonSep 6, 2025
      Report the fault to the manufacturer´s service department.
  • K
    Katelyn MillerSep 8, 2025
    What causes an EEprom fault on E.L.B. F-350?
    • J
      Jennifer SimpsonSep 8, 2025
      If the EEprom is defective, and the values of the same variable differ in all three Eeproms, report the fault to the manufacturer´s service department.

Summary

1 Introduction

EEx-p Controller F-351 Overview

Introduces the EEx-p controller F-351, its features, and ATEX approval.

2 Safety Information and Notes

Key Safety Precautions

Contains important warnings, cautions, and mandatory procedures for safe operation.

3 Structure and Function

Functional Description and Operation

Explains the controller's function, operation, and behavior during normal and fault conditions.

Faults and Troubleshooting

Provides detailed information on system faults, their causes, and remedies.

4 Use for the Intended Purpose

Maintenance and Safety

Covers safety precautions, cleaning procedures, and relay contact testing.

5 Parametrizing the Controller

Menu Navigation and Settings

Overview of menus, factory settings, and parameter modification using Wheel Shuttle.

Parameter Configuration

Details settings for language, purge volume, pressure, flow, display, relay, switch, regulation, and bypass.

6 Installation and Setting-to-Work

System Circuitry and Data

Shows system circuitry diagrams and technical data for controller and regulator.

7 Digital Controller F-220.2 B

Technical Data

Lists technical specifications for the F-220.2B digital controller, including voltage, current, and environmental ratings.