ANALOG 4mA and 20mA POINT ADJUSTMENT PARAMETERS
Each analog output is calibrated to 4mA and 20mA points, so each of the up to four analog
outputs has a 4mA and 20mA point setting – see the parameters below:
EI-1000
ANALOG OUTPUT 4.00 mA (ZERO) ADJUSTMENT: EI-1000
PARAMETER EI-1000: Ao.x (x = 1,2,3, or 4) Press
Set the left 4.00 mA analog output point using the up & down arrow pushbuttons. The display
will not show any indication that the left analog output is changing which is why one should
have a "mA" meter (i.e., DMM) connected to the appropriate output. The mA output range is
approximately 4.0 mA +/- 1.0 mA.
ANALOG OUTPUT 20.00 mA (SPAN) ADJUSTMENT: EI-1000
PARAMETER EI-1000: Ao.x (x = 1,2,3, or 4)
Set the left 20.00 mA analog output point using the right up & down arrow pushbuttons. The
display will not show any indication that the left analog output is changing which is why one
should have a "mA" meter (i.e. DMM) connected to J3-1 & J3-2. The mA output range is
approximately 20.0 mA +/- 1.0 mA.
EI-2000
ANALOG OUTPUT 4.00 mA (ZERO) ADJUSTMENT: EI-2000
PARAMETER EI-2000: "AO x" " 4.00" (x = 1,2,3, or 4)
Set the left 4.00 mA analog output point using the right up & down arrow pushbuttons. The
display will not show any indication that the left analog output is changing which is why one
should have a "mA" meter (i.e., DMM) connected to the appropriate output. The mA output
range is approximately 4.0 mA +/- 1.0 mA.
ANALOG OUTPUT 20.00 mA (SPAN) ADJUSTMENT: EI-2000
PARAMETER EI-2000: "AO x" "20.00" (x = 1,2,3, or 4)
Set the left 20.00 mA analog output point using the right up & down arrow pushbuttons. The
display will not show any indication that the left analog output is changing which is why one
should have a "mA" meter (i.e. DMM) connected to J3-1 & J3-2. The mA output range is
approximately 20.0 mA +/- 1.0 mA.