The following response returns the contents of Demand Time as 1, But see also “Exception
Response” later.
Data, High Reg, High Byte
3.9.2 Write Holding Registers
MODBUS Protocol code 10 (16 decimal) writes the contents of the 4X registers.
Example
The following query will set the Demand Period to 60, which effectively resets the Demand
Time:
Data, High Reg, High Byte
Note: Data must be written in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to write a floating point variable. If the “Starting Address” or the
“Number of points” is odd then the query will fall in the middle of a floating point variable the
product will return an error message. In general only one floating point value can be written per
query
The following response indicates that the write has been successful. But see also “Exception
Response”later.