I.B. 32-255-1G
Page 2
Effective 12/02
BOOK MUST BE CAREFULLY READ AND FOL-
LOWED IN ORDER TO OBTAIN OPTIMUM PERFOR-
MANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
BREAKER ELEMENTS.
THE CIRCUIT BREAKER ELEMENTS DESCRIBED IN
THIS BOOK ARE DESIGNED AND TESTED TO OPER-
ATE WITHIN THEIR NAMEPLATE RATINGS. OPERA-
TION OUTSIDE OF THESE RATINGS MAY CAUSE
THE EQUIPMENT TO FAIL, RESULTING IN DEATH,
BODILY INJURY AND PROPERTY DAMAGE.
ALL SAFETY CODES, SAFETY STANDARDS AND/OR
REGULATIONS AS THEY MAY BE APPLIED TO THIS
TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED
TO.
!
WARNING
1-3 TYPE VCP-W VACUUM CIRCUIT BREAKER ELEMENT RATINGS (TABLES 1.1, 1.2, 1.3, 1.4, 1.5 AND 1.6)
Table 1.1 (ANSI Standards
) Type VCP-W Vacuum Circuit Breaker Through 15 kV Rated Symmetrical Current Basis
Applicable ANSI Standards C37.04-1979, C37.09-1979 and C37.06-1987.
Operating Duty Cycle CO-15 seconds-CO. Operating Time Values: Opening
30-45 ms, Closing 45-60 ms and Reclosing 18 cycles (300 rms).
Non-standard circuit breakers with High Close and Latch (momentary)
rating for special applications.
Consult Application Data 32-265 for further information.
Optional interrupting time of 3 cycles is available.
Also 3-second short time current carrying capability.
Identification Rated Values
Circuit Nominal Nominal Voltage Insulation Level Current Inter- Permis- Maximum Current Values
Breaker Voltage 3-Phase Maximum Voltage Withstand Test Continuous Short rupting sible Voltage Maximum Closing Closing
Type Class MVA Voltage Range Voltage Current Circuit Time
Tripping Divided Symmetrical and and
Class Factor
at 60 Hz Current Delay By K Interrupting Latching Latching
(at Rated Capability Capability Capability
Max. kV) Momentary
Power Impulse K Times 2.7 K 1.6 K
Frequency Rated Short Times Times
(1 Min.) Circuit Rated Rated
Current
➂➄
Short Short
Circuit Circuit
Current Current
E K I Y E/K
kV MVA kV rms kV rms kV Peak Amperes kA rms Cycles Seconds kV rms kA rms kA Peak kA rms
50VCPW-ND250 4.16 250 4.76 1.24 19 60 1200 29 5 2 3.85 36 97 58
50VCP-W250 4.16 250 4.76 1.24 19 60 1200 29 5 2 3.85 36 97 58
2000 132
78
3000
50VCP-W350 4.16 350 4.76 1.19 19 60 1200 41 5 2 4.0 49 132 78
2000
3000
75VCP-W500 7.2 500 8.25 1.25 36 95 1200 33 5 2 6.6 41 111 66
2000
3000
150VCP-W500 13.8 500 15 1.30 36 95 1200 18 5 2 11.5 23 62 37
2000 97
58
3000
150VCP-W750 13.8 750 15 1.30 36 95 1200 28 5 2 11.5 36 97 58
2000 130
77
3000
150VCP-W1000 13.8 1000 15 1.30 36 95 1200 37 5 2 11.5 48 130 77
2000
3000
150VCP-W1500
(63)
13.8 1500 15 1.00 36 95 1200 63 5 2 15.0 63 170 101
2000
3000

Table of Contents