I.B. 32-255-1G
Page 45
Effective 12/02
6-11 TROUBLESHOOTING CHART
Fails To Trip
Trip Sound Trip Mechanism Trip Bar, Trip Latch
But No Trip (Jammed)
Pole Shaft
(Jammed)
Operating Rod Assembly
(Broken or pins out)
Vacuum Interrupter
(One or more Welded)
Undesirably Trips
Control Circuit Control Power
(CS/T Switch, remains made)
Mechanism Trip Coil Clapper
(Not resetting)
Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
Trip Bar Reset Spring
(Loss of torque)
SYMPTOM INSPECTION AREA PROBABLE DEFECTS