6. Appendices
6.1 Technical specications
5PX 1500i RT2U 5PX 2000i RT2U 5PX 2200i RT2U 5PX 3000i RT2U 5PX 3000i RT3U
Output Power 1500 VA
1350 W
2000 VA
1800 W
2200 VA
1980 W
3000 VA
2700 W
3000 VA
2700 W
AC Input power
l Rated input voltage
l Input voltage range
l input frequency range
Single phase 200-240 V
160 to 294 V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
l Voltage
l Frequency
230 V (-10/+6 %)
(3)
50/60 Hz ±0.1 Hz
Battery
(sealed lead acid,
maintenance free)
l Standard
l Additional
modules possible
(up to 4 EBM)
4 x 12 V
7.2 Ah
4 x 12 V
9 Ah
6 x 12V
9Ah
5PX EBM 48V RT2U
(4)
5PX EBM 72 V
RT2U
(5)
5PX EBM 72 V
RT3U
(5)
Environnement
l Operating
temperature range
l Storage
temperature range
l Relative humidity
l Noise level
0 to 40 °C
-15 to +50 °C
20 to 90 % (without condensation)
< 45 dBA < 50 dBA
(1) The high and low thresholds can be adjusted using UPS settings (up to 150-294 V).
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240 V (23 % derating at 200 V, and 10 % derating at 208 V on 2.2 kVA, 17 % derating at 200 V
on 3 kVA)
(4) 5PX EBM 48V RT2U: 2 strings, each 4 x 12 V / 9 Ah.
(5) 5PX EBM 72V RT2U and 5PX EBM 72V RT3U: 2 strings, each 6 x 12 V / 9 Ah.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger Inverter
Battery