Firmware upgrade procedure
Eaton®setUPS_5PX_firmware_upgrade_rev_02 Page 13/14
12. Trouble shooting
The firmware upgrade is stopped during the process :
→ restart the firmware upgrade process and the upload starts again.
The setUPS software doesn’t recognize your 5PX UPS : the computer installed a
wrong UPS driver (MGE USB UPS) :
you have to restart setUPS to have the correct driver installed (Eaton UPS 0463-L).
In the firmware section, the Upload firmware” button is not available :
UPS is not powered OFF, refer to the section4. Power OFF the UPS
The display is completely blue and it is difficult to read text on it :
Initial settings :
It is necessary to set UPS local settings, possibly before to adjust the contrast.
Language
Bad contrast Good contrast (for reference)
Output voltage
Bad contrast Good contrast (for reference)