Operation
Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F www.eaton.com/powerquality 71
Signal Inputs [empty] [Logic]
(see”Programmable Signal Inputs”on page 61)
<empty>
Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Modem Config Modem Setup <Not Installed>
Set Modem Call Events Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password None
Battery Setup Number of Internal Battery Strings 6
Internal Battery Capacity [1 through 65535 watts per cell] 34W/cell
Number of External Battery Strings
(see ”Configuring the UPS for EBCs”on page 75)
0
External Battery Capacity 120W/cell
Battery Low Alarm Level [1.750 through 1.950 volts per
cell]
1.880 V/cell
Battery Charging [ABM cycling/constant] ABM cycling
Automatic Battery Tests [Enabled/Disabled]
Enabled automatically runs the battery test once a month.
Enabled
Full Power Battery Test [Enabled/Disabled] Enabled
Start Screen Eaton logo
Mimic screen
Eaton logo
User Password Enabled/Disabled
If Enabled is selected, the password is USER.
Disabled
Audible Alarms Normal Sound/Disabled Normal Sound
Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%
Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%
Nominal Output Frequency 50 Hz or 60 Hz 60 Hz
Synchronization Enabled/Disabled Enabled
Synchronization Window 0.5 through 3.0 Hz
(0.1 Hz increments)
2.0 Hz
Unsynchronized Transfer to Bypass Allowed/Not Allowed Not Allowed
Output Frequency Slew Rate 0.1 though 5 hertz per second
(0.1 Hz increments)
0.5 Hz/s
Usage of Bypass Enabled/Disabled Enabled
Transfer to Bypass When Overload After a delay/Immediately After a delay
Control Commands from X-Slot1 Allowed/Disabled Allowed
Control Commands from X-Slot2/
Serv
Allowed/Disabled Allowed
X-Slot Signal Input Activation Delay 0 through 65 seconds 5s
Input Signal Delayed Shutdown
Delay
1 through 65535 seconds 120s
Table 7. User Settings (Continued)
Description Available Settings Default Setting