Eaton 93E UPS 15-80 kVA (380/400/415 V) Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved. Revision: 001
Document ID: 614-01975-00
128 (133)
10.2.2 UPS environmental
Operating temperature
0ºC… +40ºC
35ºC maximum continuous
40ºC for 8 hours.
Altitude temperature 40°C
The recommended operating
temperature is 25°C (77°F).
Battery: 5 to 25°C
Operating altitude
1 000 m above sea level at +40°C.
Maximum 2 000 m with 1% derating
per each additional 100 m.
Storage temperature
-15 to +55°C, excluding batteries
(prolonged storage above 40°C causes
rapid battery self-discharge)
Relative humidity (operating and
storage)
5% to 95%, non-condensing
Acoustical noise
55 dB (15-20 kVA)
62 dB (30-40 kVA)
65 dB (60-80 kVA)
at a 1 m distance, per ISO 7779
EMC
Meets IEC 62040-2 2005 C3
Internal battery recharging during
storage
Batteries must be re-charged at 6
month intervals.
Do not store units with internal
batteries longer than 6 months without
re-charging.
Check the latest charging date on the
delivery package.
10.2.3 UPS input
Operating input voltage
380 / 400 / 415 Vac
Input voltage range
190 / 330276 / 478V (-15%, +20%) at
a 100% load
116 / 201-276 / 478V (-50%, +20%) at
a 50% load
Operating input frequency range
50 / 60 Hz
Input frequency range
40-72 Hz