The output is
overload
(Bypass mode)
102%~110% : overload alarm
110%~130% : turned off in 5 minutes
130%~150% : turned off in 15s
>150% : turned off in 300ms
Percentages are based on the nominal current values in Bypass mode.
< 3% THDV (linear load)
< 5% THDV (nonlinear load)
Table 7. Electrical Output Connection
Master output: (4) IEC10A
Partition 1: (2) IEC10A
Partition 2: (2) IEC10A
Master output: (4) IEC10A + (1)
IEC16A
Partition 1: (2) IEC10A + (1) IEC16A
Partition 2: (2) IEC10A
Table 8. Environment and Safety
IEC/EN 62040-1
IEC/EN 62040-2: Cat: C1
IEC/EN 62040-3
UL1778 5
th
edition
CSA 22.2
CISPR22 Class B
FCC part 15 Class B / ICES-003
IEC 61000-4-2, (ESD): 8kV contact discharge/15kV air discharge
IEC 61000-4-3, (radiation field): 10V/m
IEC 61000-4-4, (EFT): 4kV
IEC 61000-4-5, (lightning strike): 2kV differential mode discharge/4kV common
mode discharge
IEC 61000-4-6, (electromagnetic field): 10V
IEC 61000-4-8, (conductive magnetic field): 30A/m
*Applicable to output power cords less than 10m in length.
CE / cULus / EAC / RCM / KC / Energy Star
0 to 40°C (32 to 104°F) in Online mode and decreasing linearly with the
increase of altitude
Note: The output is switched to bypass in the event of device overheat.
0 to 35°C (32 to 95°F) with battery
-15 to 60°C (5 to 140°F) without battery
-25 to 55°C (-13 to 130°F)
0 to 96% (non-condensing)
Maximum altitude of 3,000m (9,843ft) without derating at room temperature of
35°C (95°F)
Maximum altitude of 10,000m (32,808ft)
Usually < 47dBA at 1 meter