23
Note:
1. For single input connection, please select the larger conductor size cross-
section.
2. UPS output cable length is recommended not to exceed 10m.
3. UPS default input/output phase mode is: mode 3-1(single source).
4. If the load in a 3-phase output mode is unbalanced, the L wire of the bypass
and output may exceed the rated current by 1.732 times. The corresponding
protection device and wiring cable must be determined according to the
standards of the region and the actual situation of the user.
Please refer to the following table for conductor’s terminal selection:
Recommended circuit breaker and contactor current specifications:
Model name
Input mode
Breaker
Contactor
9SX 15KPM(AU)
1 phase main input
D type 125A
125A
3 phase main input
D type 63A
63A
1 phase bypass input
D type 100A
100A
3 phase bypass input
D type 40A
40A
9SX 20KPM(AU)
1 phase main input
D type 160A
160A
3 phase main input
D type 63A
63A
1 phase bypass input
D type 125A
125A
3 phase bypass input
D type 63A
63A
3-3
10
10
10
10
10
10
10
10
10
10
1-1
50
50
25
25
50
25
25
25
10
10
1-3
50
50
10
10
50
10
10
10
10
10
Conductor cross-section (Unit: mm²)
Ring terminal type
6
DRNB6-6
10
DRNB6-10
16
DRNB8-16
25
DRNB8-25
35
DRNB8-35
50
DRNB8-50