EasyManua.ls Logo

Eaton Box 1 - C600 M Wiring Kit Diagrams: C30 CN Contactor Types; Lighting Contactor C30 CN, Electrically Held; Lighting Contactor C30 CN, Mechanically Held 3-Wire Control

Eaton Box 1
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Instructions and Operation P52899
Effective July 2019
Box 1 and Box 2 non-combination enclosed
control and C600M cover control kit wiring
EATON www.eaton.com
C600M wiring kit diagrams—Box 2
L1
R1
10A
10A
X2
X2
1
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR
CONNECTING POWER! THIS PRODUCT CAN BE FACTORY OR FIELD
CONFIGURED FOR MULTIPLE CONTROL MODES OR CONTROL
VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
SEPARATE CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: CONNECT SEPARATE CONTROL
LINES TO THE NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE
A2 TERMINAL ON THE COIL.
FOR COIL VOLTAGES GREATER THAN 120V: REMOVE WIRE "C2" IF
SUPPLIED. IF WIRE "C1" IS TERMINATED ON L1, DISCONNECT FROM
L1. CONNECT SEPARATE CONTROL LINES TO THE "C1" WIRE OR
APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM AND TO THE
A2 TERMINAL ON THE COIL.
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: ADD WIRE "C2" IF NOT
SUPPLIED. ADD CONNECTOR BETWEEN L1 TERMINAL AND THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. OR APPROPRIATE
PILOT DEVICE TERMINAL PER DIAGRAM.
FOR COIL VOLTAGES GREATER THAN 120V: ADD WIRE "C1" AND "C2"
IF NOT SUPPLIED.
OPTION FOR RED RUN LIGHT (RED TYPICAL)
1
2
REQUIRED FOR 480V OPTION
OPTION FOR OFF LIGHT (GREEN TYPICAL)
3
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR
CONTROL POWER WIRING OPTIONS
COVER CONTROL
OPTION SHOWN
1
2
3
R
G
NC1 NC2
NO4
NO3
2/13 3/14
A2
A1
X2X1
1
2
X2X1
1
2
6261
1
2
1
2
OFF ON
M1
M1
RUN
OFF
M1
RED/BLK
RED/BLK
RED
RED
RED RED
BLK/WHT
BLK/WHT
RED
RED
YEL BLK
RED
*
*
RED
RED
LIGHTING CONTACTOR C30CN_ ELECTRICALLY HELD. REF.: OFF/ON OVAL PUSHBUTTON RED RUN GRN OFF
Fuse
Fuse
X2
X2
1
3/L2 OR SEPARATE CONTROL
1/L1 OR SEPARATE CONTROL
1/L1 OR SEPARATE CONTROL
240VAC
3/L2 OR SEPARATE CONTROL
240VAC
10A
10A
X2
X2
1
3
4
REF:-COMBINATION OF COIL VOLTAGE(B) 240VAC TO CONTROL MODULE VOLTAGE 200-277V AC (H0)
DASHED COMPONENTS ARE OPTIONAL. USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
1
OPTION FOR RED RUN LIGHT (RED TYPICAL)
REFER COIL VOLTAGE AND CONTROL MODULE VOLTAGE
COMBINATION TABLE FOR BOTH VOLTAGE RANGES.
2
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER! THIS PRODUCT CAN BE FACTORY OR
FIELD CONFIGURED FOR MULTIPLE CONTROL MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
SEPARATE CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: CONNECT SEPARATE CONTROL LINES TO THE NO. 61 TERMINAL ON THE TOP
ADDER AUX. AND TO THE A2 TERMINAL ON THE COIL.
FOR COIL VOLTAGES GREATER THAN 120V: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE "C1" IS TERMINATED ON L1,
DISCONNECT FROM L1. CONNECT SEPARATE CONTROL LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE
TERMINAL PER DIAGRAM AND TO THE A2 TERMINAL ON THE COIL.
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: ADD WIRE "C2" IF NOT SUPPLIED. ADD CONNECTOR BETWEEN L1 TERMINAL AND
THE NO. 61 TERMINAL ON THE TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
FOR COIL VOLTAGES GREATER THAN 120V: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
BASE COIL VOLTAGE AND CONTROL MODULE VOLTAGE COMBINATION TABLE
BASE COIL VOLTAGE
*
WIRING
CONTROL MODULE
VOLTAGE
WIRING COMBINATION
A 120V 60Hz S A0 110-120VAC S AA0
SS
B 240V 60Hz
C H0 200-277VAC C
BH0
CC
E 208V 60Hz EH0
H 277V 60Hz HH0
T 24V 60Hz S T0 24VAC S TT0
SS
2
* S- SEPARATE CONTROL, C- COMMON CONTROL
ELECTRONIC
MODULE
BLK
BLK
BLK
COVER CONTROL
OPTION SHOWN
1
REFERENCE NOTES BELOW FOR
CONTROL POWER WIRING OPTIONS
R
G
A2A1
P4
P2
P3
R1
L1
P1
P5
R1
L1
M
RUN
OFF
M
M
M
M
LIGHTING CONTACTOR C30CN_ MECHANICALLY HELD 3-WIRE CONTROL. REF.: OFF/ON OVAL RED RUN GRN OFF.
*
*
RED
RED
BLK/WHT
RED/BLK
RED
RED
RED
RED
RED
RED
RED
RED
RED/BLK
BLK/WHT
RED
ON
OFF
Fuse
Fuse
X2
X2
3
4
1
ote:N Source drawing reference wiring diagrams 288257.