11
Instructions and Operation P52899
Effective July 2019
Box 1 and Box 2 non-combination enclosed
control and C600M cover control kit wiring
EATON www.eaton.com
C600M wiring kit diagrams—Box 2
1/L1 OR SEPARATE CONTROL
240VAC
3/L2 OR SEPARATE CONTROL
240VAC
10A
10A
X2
X2
1
3
REF:-COMBINATION OF COIL VOLTAGE(B) 240VAC TO CONTROL MODULE VOLTAGE 200-277V AC (H0)
DASHED COMPONENTS ARE OPTIONAL. USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
1
OPTION FOR RED RUN LIGHT (RED TYPICAL)
REFER COIL VOLTAGE AND CONTROL MODULE VOLTAGE
COMBINATION TABLE FOR BOTH VOLTAGE RANGES.
2
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER! THIS PRODUCT CAN BE FACTORY
OR FIELD CONFIGURED FOR MULTIPLE CONTROL MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR
COIL VOLTAGE.
SEPARATE CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: CONNECT SEPARATE CONTROL LINES TO THE NO. 61 TERMINAL ON THE TOP
ADDER AUX. AND TO THE A2 TERMINAL ON THE COIL.
FOR COIL VOLTAGES GREATER THAN 120V: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE "C1" IS TERMINATED ON L1,
DISCONNECT FROM L1. CONNECT SEPARATE CONTROL LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE
TERMINAL PER DIAGRAM AND TO THE A2 TERMINAL ON THE COIL.
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: ADD WIRE "C2" IF NOT SUPPLIED. ADD CONNECTOR BETWEEN L1 TERMINAL
AND THE NO. 61 TERMINAL ON THE TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
FOR COIL VOLTAGES GREATER THAN 120V: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
BASE COIL VOLTAGE AND CONTROL MODULE VOLTAGE COMBINATION TABLE
BASE COIL VOLTAGE
*
WIRING
CONTROL MODULE
VOLTAGE
WIRING COMBINATION
A 120V 60Hz S A0 110-120VAC S AA0
SS
B 240V 60Hz
C H0 200-277VAC C
BH0
CC
E 208V 60Hz EH0
H 277V 60Hz HH0
T 24V 60Hz S T0 24VAC S TT0
SS
2
* S- SEPARATE CONTROL, C- COMMON CONTROL
ELECTRONIC
MODULE
NOT USED
BLK
BLK
REFERENCE NOTES BELOW FOR
CONTROL POWER WIRING OPTIONS
COVER CONTROL
OPTION SHOWN
1
R
G
OX
A2A1
P4
P2
P3
R1
L1
P1
P5
NO4
NO3
R1
M
RUN
OFF
M
M
M
LIGHTING CONTACTOR C30CN_ MECHANICALLY HELD 2-WIRE CONTROL. REF.: OFF/ON 2-POSITION SELECTOR SWITCH RED RUN GRN OFF
RED
*
*
RED
RED
RED
RED
RED
RED/BLK
BLK/WHT
BLK/WHT
RED/BLK
RED
RED
RED
Fuse
Fuse
3
1
X2
X2
ONOFF
ote:N Source drawing reference wiring diagrams 288257.