Instructions and Operation P52899
Effective July 2019
Box 1 and Box 2 non-combination enclosed
control and C600M cover control kit wiring
EATON www.eaton.com
C600M wiring kit diagrams—Box 2
1/L1 OR SEPARATE CONTROL
240VAC
3/L2 OR SEPARATE CONTROL
240VAC
10A
10A
REMOTE
SWITCH
X2
X2
1
3
REF:-COMBINATION OF COIL VOLTAGE(B) 240VAC TO CONTROL MODULE VOLTAGE 200-277V AC (H0)
DASHED COMPONENTS ARE OPTIONAL. USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
1
OPTION FOR RED RUN LIGHT (RED TYPICAL)
REFER COIL VOLTAGE AND CONTROL MODULE VOLTAGE
COMBINATION TABLE FOR BOTH VOLTAGE RANGES.
2
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING POWER! THIS PRODUCT CAN BE FACTORY OR
FIELD CONFIGURED FOR MULTIPLE CONTROL MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE FOR COIL VOLTAGE.
SEPARATE CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: CONNECT SEPARATE CONTROL LINES TO THE NO. 61 TERMINAL ON THE TOP ADDER
AUX. AND TO THE A2 TERMINAL ON THE COIL.
FOR COIL VOLTAGES GREATER THAN 120V: REMOVE WIRE "C2" IF SUPPLIED. IF WIRE "C1" IS TERMINATED ON L1,
DISCONNECT FROM L1. CONNECT SEPARATE CONTROL LINES TO THE "C1" WIRE OR APPROPRIATE PILOT DEVICE TERMINAL
PER DIAGRAM AND TO THE A2 TERMINAL ON THE COIL.
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: ADD WIRE "C2" IF NOT SUPPLIED. ADD CONNECTOR BETWEEN L1 TERMINAL AND THE
NO. 61 TERMINAL ON THE TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
FOR COIL VOLTAGES GREATER THAN 120V: ADD WIRE "C1" AND "C2" IF NOT SUPPLIED.
BASE COIL VOLTAGE AND CONTROL MODULE VOLTAGE COMBINATION TABLE
BASE COIL VOLTAGE
*
WIRING
CONTROL MODULE
VOLTAGE
WIRING COMBINATION
A 120V 60Hz S A0 110-120VAC S AA0
SS
B 240V 60Hz
C H0 200-277VAC C
BH0
CC
E 208V 60Hz EH0
H 277V 60Hz HH0
T 24V 60Hz S T0 24VAC S TT0
SS
2
* S- SEPARATE CONTROL, C- COMMON CONTROL
ELECTRONIC
MODULE
BLK
NOT USED
FACTORY INSTALLED JUMPER.
CUSTOMER TO DISCONNECT JUMPER FROM NO3 OF
AUTO AND CONNECT REMOTE SWITCH AS SHOWN.
IF NOT DISCONNECTED, "AUTO" WILL OPERATE
EQUIVALENTLY TO "HAND".
BLK
COVER CONTROL
OPTION SHOWN
1
REFERENCE NOTES BELOW FOR
CONTROL POWER WIRING OPTIONS
R
G
XOO
OOX
A2A1
P4
P2
P3
R1
L1
P1
P5
NO4
NO3
NO4
NO3
R1
M
RUN
OFF
M
M
M
LIGHTING CONTACTOR C30CN_ MECHANICALLY HELD 2-WIRE CONTROL. REF.: HAND/OFF/AUTO OR TEST/OFF/AUTO 3-POSITION SELECTOR SWITCH RED RUN GRN OFF
*
*
RED
RED
RED
RED
RED
RED
RED
RED/BLK
BLK/WHT
BLK/WHT
RED/BLK
RED
RED
RED
YLW
Fuse Fuse
X2
X2
1
3
AUTO
0
HAND
CONTROL POWER WIRING NOTES
CAUTION
READ AND FOLLOW INSTRUCTIONS PRIOR TO WIRING OR CONNECTING
POWER! THIS PRODUCT CAN BE FACTORY OR FIELD CONFIGURED FOR
MULTIPLE CONTROL MODES OR CONTROL VOLTAGES. CHECK NAMEPLATE
FOR COIL VOLTAGE.
SEPARATE CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: CONNECT SEPARATE CONTROL LINES
TO THE NO. 61 TERMINAL ON THE TOP ADDER AUX. AND TO THE A2
TERMINAL ON THE COIL.
FOR COIL VOLTAGES GREATER THAN 120V: REMOVE WIRE "C2" IF SUPPLIED.
IF WIRE "C1" IS TERMINATED ON L1, DISCONNECT FROM L1. CONNECT
SEPARATE CONTROL LINES TO THE "C1" WIRE OR APPROPRIATE PILOT
DEVICE TERMINAL PER DIAGRAM AND TO THE A2 TERMINAL ON THE COIL.
COMMON CONTROL POWER
FOR COIL VOLTAGES 120V AND LESS: ADD WIRE "C2" IF NOT SUPPLIED. ADD
CONNECTOR BETWEEN L1 TERMINAL AND THE NO. 61 TERMINAL ON THE
TOP ADDER AUX. OR APPROPRIATE PILOT DEVICE TERMINAL PER DIAGRAM.
FOR COIL VOLTAGES GREATER THAN 120V: ADD WIRE "C1" AND "C2"
IF NOT SUPPLIED.
COVER CONTROL
OPTION SHOWN
NO3
RED
RED
OFF
L1 OR SEPARATE CONTROL
1
OPTION FOR RED RUN LIGHT (RED TYPICAL)
1
2
REQUIRED FOR 480V OPTION
CONTROL
MODULE
DASHED COMPONENTS ARE OPTIONAL
USE AS REQUIRED FOR SELECTED COVER CONTROL OPTIONS
REFERENCE NOTES BELOW FOR
CONTROL POWER WIRING OPTIONS
1
2
2
R
G
A2
A1
NO4
NO4
NO3
A2
A1
~
~
-
+
1
2
1
2
X2
X1
X2X1
1
2
1
2
M
ON
M
M
L2
M
M
RUN
OFF
M
RED
RED
RED
BLK
WHT
BLK
RED
RED/BLK
RED
RED
RED/BLK
RED RED
BLK/WHT
BLK/WHT
LIGHTING CONTACTOR MAGNETICALLY HELD. REF.: OFF/ON OVAL PUSHBUTTON RED RUN GRN OFF
YLW
2
3
OFF
1
ON
L2 OR SEPARATE CONTROL
X2
X2
X2
X2
1
ote:N Source drawing reference wiring diagrams 288257.