Technical Data MN019001EN
Effective November 2015
Bussmann series
PV Combiner box
EATON www.eaton.com
24 string monitoring units
Interface parameters
The type S1 string monitoring module PVCBM-GR24 supports the
modbus RTU protocol with the following interface parameters:
Baud rate 1200 to 38400 Bd
Format 8n1, 8e1 or 8o1
Max. cable length 1.2km
Unit load 1/8
Byte order MSBit-LSBit
Word order LSByte-MSByte
Address range 1 – 247
Max. frame length 256 Bytes
The following are supported as function codes:
03 Read contents of a holding register
04 Read contents of an input register
06 Write contents of a R/W register (preset single register)
For reading the registers the following therefore arises:
Address basis Function code
for reading
Function code
for writing
Input register
30001 0x04 -
Holding register
40001 0x03 0x06
List of registers and functions
Abbreviations used Explanation
UINT16 Data type unsigned integer. 16 bit
UINT32 Data type unsigned integer. 32 bit
Float32 Data type floating, 32 bit
R Only read access possible (read only)
R/W Read and write access possible (read/write)
Register
(integer)
Data
type
Channel (descrip-
tion)
Possible values Unit R/W
0000 UINT16 Digital input 01
(main switch)
0: OFF
1: ON
R
0001 UINT16 Digital input 02
(1000V DC overvolt-
age protection
0: NOK
1: OK
R
0003 UINT16 Digital input 03 0, 1 R
0004,0005 Float32 Current I
1
-30.00 … +30.00 A R
0006, 0007 Float32 Current I
2
-30.00 … +30.00 A R
0008, 0009 Float32 Current I
3
-30.00 … +30.00 A R
0010, 0011 Float32 Current I
4
-30.00 … +30.00 A R
0012, 0013 Float32 Current I
5
-30.00 … +30.00 A R
0014, 0015 Float32 Current I
6
-30.00 … +30.00 A R
0016, 0017 Float32 Current I
7
-30.00 … +30.00 A R
0018, 0019 Float32 Current I
8
-30.00 … +30.00 A R
0020, 0021 Float 32 Current I
9
-30.00 … +30.00 A R
0022, 0023 Float32 Current I
10
-30.00 … +30.00 A R
0024, 0025 Float32 Current I
11
-30.00 … +30.00 A R
0026, 0027 Float32 Current I
12
-30.00 … +30.00 A R
0028, 0029 Float32 Current I
13
-30.00 … +30.00 A R
0030, 0031 Float32 Current I
14
-30.00 … +30.00 A R
0032, 0033 Float32 Current I
15
-30.00 … +30.00 A R
0034, 0035 Float32 Current I
16
-30.00 … +30.00 A R
0036, 0037 Float32 Current I
17
-30.00 … +30.00 A R
0038, 0039 Float32 Current I
18
-30.00 … +30.00 A R
0040, 0041 Float32 Current I
19
-30.00 … +30.00 A R
0042, 0043 Float32 Current I
20
-30.00 … +30.00 A R
0044, 0045 Float32 Current I
21
-30.00 … +30.00 A R
0046, 0047 Float32 Current I
22
-30.00 … +30.00 A R
0048, 0049 Float32 Current I
23
-30.00 … +30.00 A R
Register
(integer)
Data
type
Channel (descrip-
tion)
Possible values Unit R/W
0050, 0051 Float32 Current I
24
-30.00 … +30.00 A R
0052, 0053 Float32 Summed current -480.00 … +480.00 A R
0054, 0055 Float32 Voltage 0 … 1000.0 V R
0056, 0057 Float32 Power 0 … 480,000 W R
0058, 0059 Float32 Temperature 1 -40.0 … +160.0 °C R
0060, 0061 Float32 Temperature 2 -40.0 … +160.0 °C R
0062, 0063 UINT32 Firmware date 0xDDMMYYYY
Example:
0x040507DB
04.05.2011
R
0064, 0065 UINT32 Software version 0xBBBBMMNN
Example:
0x12510102
V1.02.1251
R
0066 UINT16 Error code 1: OK
≠1: NOK
R
0067 UINT16 Calibration status 1: OK
2: Busy
>2: Error number
R
0069 UINT16 Sync ID
1)
User code of Reg.
0302
R
0070, 0071 Float32 Sync_current I
1
1)
-30.00 … +30.00 A R
0072, 0073 Float32 Sync_current I
2
-30.00 … +30.00 A R
0074, 0075 Float32 Sync_current I
3
-30.00 … +30.00 A R
0076, 0077 Float32 Sync_current I
4
-30.00 … +30.00 A R
0078, 0079 Float32 Sync_current I
5
-30.00 … +30.00 A R
0080, 0081 Float32 Sync_current I
6
-30.00 … +30.00 A R
0082, 0083 Float32 Sync_current I
7
-30.00 … +30.00 A R
0084, 0085 Float32 Sync_current I
8
-30.00 … +30.00 A R
0086, 0087 Float32 Sync_current I
9
-30.00 … +30.00 A R
0088, 0089 Float32 Sync_current I
10
-30.00 … +30.00 A R
0090, 0091 Float32 Sync_current I
11
-30.00 … +30.00 A R
0092, 0093 Float32 Sync_current I
12
-30.00 … +30.00 A R
0094, 0095 Float32 Sync_current I
13
-30.00 … +30.00 A R
0096, 0097 Float32 Sync_current I
14
-30.00 … +30.00 A R
0098, 0099 Float32 Sync_current I
15
-30.00 … +30.00 A R
0100, 0101 Float32 Sync_current I
16
-30.00 … +30.00 A R
0102, 0103 Float32 Sync_current I
17
-30.00 … +30.00 A R
0104, 0105 Float32 Sync_current I
18
-30.00 … +30.00 A R
0106, 0107 Float32 Sync_current I
19
-30.00 … +30.00 A R
0108, 0109 Float32 Sync_current I
20
-30.00 … +30.00 A R
0110, 0111 Float32 Sync_current I
21
-30.00 … +30.00 A R
0112, 0113 Float32 Sync_current I
22
-30.00 … +30.00 A R
0114, 0115 Float32 Sync_current I
23
-30.00 … +30.00 A R
0116, 0117 Float32 Sync_current I
24
-30.00 … +30.00 A R
0118, 0119 Float32 Sync_summed_cur-
rent
-480 … +480 A R
0120, 0121 Float32 Sync_voltage 0 … 1000.0 V R
0122, 0123 Float32 Sync_power 0 … 480.000 W R
0124, 0125 Float32 Sync_temperature 1 -40.0 … +160.0 °C R
0126, 0127 Float32 Sync_temperature 2 -40.0 … +160.0 °C R
0149 UINT16 Relay output 0: OFF
1: ON
R/W
0200 UINT16 Device identification 2008 (124)
2007 (208)
2006 (116)
2005 (108)
R
0202 UINT16 Serial number low e.g. 14148 R
0203 UINT16 Serial number high e.g. 4 R
0205 UINT16 Modbus address 1 … 254 R/W
0206 UINT16 Configuration for
current measurement
register
2)
0: default
1: fast
R/W