20
Technical Data MN019001EN
Effective November 2015
Bussmann series
PV Combiner box
EATON www.eaton.com
NOTICE
Replaceable parts
Fuses
Eaton recommends replacing blown PV Fuses with Eaton’s
Bussmann series PV Fuse links. Fuse links must be of the same
rating as that which is being replaced, and must be for the same
system voltage. A complete list of Eaton’s Bussmann series PV
fuse links for 600VDC and 1000VDC systems is shown below.
System
Voltage
Fuse
Size
Current
Rating
Part No. Description
1000 VDC
10 x 38
1A PV-1A10F 10x38 1000VDC 1A gPV Fuse
2A PV-2A10F 10x38 1000VDC 2A gPV Fuse
3A PV-3A10F 10x38 1000VDC 3A gPV Fuse
3.5A PV-3-5A10F 10x38 1000VDC 3.5A gPV Fuse
5A PV-5A10F 10x38 1000VDC 5A gPV Fuse
6A PV-6A10F 10x38 1000VDC 6A gPV Fuse
8A PV-8A10F 10x38 1000VDC 8A gPV Fuse
10A PV-10A10F 10x38 1000VDC 10A gPV Fuse
12A PV-12A10F 10x38 1000VDC 12A gPV Fuse
15A PV-15A10F 10x38 1000VDC 15A gPV Fuse
20A PV-20A10F 10x38 1000VDC 20A gPV Fuse
14 x 51
25A PV-25A14F 14x51 1000VDC 25A gPV Fuse
32A PV-32A14F 14x51 1000VDC 32A gPV Fuse
600 VDC 10 x 38
4A PVM-4 10x38 600VDC 4A gPV Fuse
5A PVM-5 10x38 600VDC 5A gPV Fuse
6A PVM-6 10x38 600VDC 6A gPV Fuse
7A PVM-7 10x38 600VDC 7A gPV Fuse
8A PVM-8 10x38 600VDC 8A gPV Fuse
9A PVM-9 10x38 600VDC 9A gPV Fuse
10A PVM-10 10x38 600VDC 10A gPV Fuse
12A PVM-12 10x38 600VDC 12A gPV Fuse
15A PVM-15 10x38 600VDC 15A gPV Fuse
20A PVM-20 10x38 600VDC 20A gPV Fuse
25A PVM-25 10x38 600VDC 25A gPV Fuse
30A PVM-30 10x38 600VDC 30A gPV Fuse
SPD modules
Your Eaton’s Bussmann series combiner box may contain a
number of surge protection devices (SPD) to protect against
damaging over voltage conditions. There are three types of SPD
available for your combiner box, PV T1, PV T1/T2, PV T2; IEC mains
T2 and Modbus RS-485 communications C2/D1. Each type of
SPD is designed to safely shunt damaging overvoltage surges
to ground, minimising the risk of harm to the equipment and
personnel.
Each SPD consists of a base and module. When a voltage surge
occurs, Eaton’s SPDs are designed so that only the module needs
to be replaced. Replacement module part numbers are as per the
table below.
BSPS31000PV PV SPD, T1, 1000V DC
Replacement module N/A
SPPVT12-06-2-PE
SPPVT12-06-2-PE-AX
PV SPD, T1/T2, 600V DC (-AX with remote)
Replacement module SPPVT12-06
SPPVT12-10-2-PE
SPPVT12-10-2-PE-AX
PV SPD, T1/T2, 1000V DC (-AX with remote)
Replacement module SPPVT12-10
SPPVT2-06-2-PE
SPPVT2-06-2-PE-AX
PV SPD, T2, 600V DC (-AX with remote),
Iscpv = 160A
Replacement module SPPVT2-06
SPPVT2-10-2-PE
SPPVT2-10-2-PE-AX
PV SPD, T2, 1000V DC (-AX with remote),
Iscpv = 160A
Replacement module SPPVT2-10
SPPVT2H-06-2-PE
SPPVT2H-06-2-PE-AX
PV SPD, T2, 600V DC (-AX with remote),
Iscpv = 1000A
Replacement module SPPVT2H-06
SPPVT2H-10-2-PE
SPPVT2H-10-2-PE-AX
PV SPD, T2, 1000V DC (-AX with remote),
Iscpv = 1000A
Replacement module SPPVT2H-10
SPCT2-280-2 IEC T2, 230V AC, 2 Pole
Replacement module SPCT2-280
SPCT2-280-1-NPE IEC T2, 230V AC, 1 Pole + 1 NPE Pole
Replacement module SPCT2-280
SPCT2-NPE60
BSPD5DINLHF RS-485 SPD for date communications
Replacement module N/A
PV T2 SPD
IEC T2 2-pole SPD
Service items
In addition to fuses and SPD modules, there are service items for
which replacements are available from Eaton. These include –
•
IP68 rated glands (input and output)
•
IP66 rated breather drains
•
IP65 rated cover for external communications port
•
Combiner box key
If you require any of these components please contact Eaton on
+44 (0)1509 882699, with your product number and unique ID
number ready.