EasyManua.ls Logo

Eaton CEAG DualGuard-S - Technical description

Eaton CEAG DualGuard-S
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
127
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
50 DualGuard-S US 7
Technical description Field
Dimensions (W x H x D): 600x400x300 mm
Colour: RAL 7035
Weight: 42 kg
Assembly: Recommended for wall mounting: 4xM8 (min.
2xM8)
Force [N]: 1861
Mounting stability [N]: 950
Degree of protection: IP54
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 230 V AC A4
Rated current (Mains): IN = 30 A
Rated voltage (Battery): 216 V DC A4
Rated current (Battery): IN =30 A
Rated Frequency: 50 or 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. connected load: At +35°C < 6,5 KW
Maximum numbers of modules:
Controller ACU DG / HMI 1 A1
PSU 1 B1
SKU.1.1 CG-S: A3
1x6A 0-7
2x3A 0-7
4x1,5A 0-7
Max. numbers luminaire circuits: 28 A3
Terminals:
ACU DG 2,5mm² Rigid/ 1,5mm² flexible A1
Luminaire circuits 4 mm² Rigid/flexible A3
Battery feed 16 mm² Rigid/flexible A4
Battery through-wiring 16 mm² Rigid/flexible A4
Mains feed 16 mm² Rigid/flexible A4
Mains through-wiring 16 mm² Rigid/flexible A4