128
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
51 DualGuard-S US SOU2
51 DualGuard-S US SOU2
The DualGuard-S US SOU2 sub-station in accordance with
EN 50171 supplies 230V / 216V AC/DC safety and escape
sign luminaires and is particularly suitable for installation
in fire compartments in buildings with a large number of
fire compartments. Thus, the decentralized design of the
system can contribute to reducing the costs for function
maintenance cabling. The automatic test device and indivi-
dual luminaire monitoring with individual status and name
indication per luminaire in conjunction with system-related
ECG / LED supply module including monitoring module
without additional data line reports and proclaims the ope-
rating states.
Consisting of:
Fire protection wall distributor with cable entry from above
and a SOU CG-S 2x4A circuit changeover.
Technical description Field
Dimensions (W x H x D): 583x295x129 mm
Colour: RAL 7032
Weight: 8,8 kg
Assembly: Recommended for wall mounting: 4xM8 (min.
2xM8)
Force [N]: 1076
Mounting stability [N]: 550
Degree of protection: IP65
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 230 V AC A1
Rated current (Mains): IN = 16 A
Rated voltage (Battery): 216 V DC A2
Rated current (Battery): IN =16 A
Rated Frequency: 50 or 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. connected load: At +35°C < 3,5 KW
Maximum numbers of modules:
SOU CG-S 2x4A 2 B-C
Max. numbers luminaire circuits: 4
Terminals:
Luminaire circuits: 4 mm² Rigid/flexible A3-4
Battery feed: 16 mm² Rigid/flexible A2
Battery through-wiring: 16 mm² Rigid/flexible A2
Mains feed: 16 mm² Rigid/flexible A1
Mains through-wiring 16 mm² Rigid/flexible A1
1 2 3 4
A
B
C