130
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
53 DualGuard-S ESF30 US 15P
53 DualGuard-S ESF30 US 15P
The DualGuard-S ESF30 US 15P sub-station with functional
integrity of 30 minutes according to EN 50171 and MLAR
supplies safety and escape sign luminaires 230V / 216V
AC/DC and is particularly suitable in building areas where
it is not possible to accommodate the safety-related distri-
bution boxes in a separate electrical operating room sepa-
rate from the general power supply. The automatic test
device and individual luminaire monitoring with individual
status and name indication per luminaire in conjunction
with system-related ECG / LED supply module including
monitoring module without additional data line reports and
additionally proclaims the operating status of the external
phase monitor modules
Consisting of:
Fire protection housing as wall cabinet with cable entry
from above, HMI touch display built-in, ACU DG controller,
PSU power supply module.
Preassembled mounting system for installation of:
Up to 15 pcs power circuit modules
Technical description Field
Dimensions (W x H x D): 1278x918x496 mm
Colour: RAL 7035
Weight: 169 kg
Assembly: Wand
Degree of protection: IP42
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 230 V AC A4
Rated current (Mains): IN = 11 A
Rated voltage (Battery): 216 V DC A4
Rated current (Battery): IN =11 A
Rated Frequency: 50 or 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. connected load: At +35°C < 2,4 KW
Maximum numbers of modules:
Controller ACU DG / HMI 1 A1
PSU 1 B2
SKU.1.1 CG-S: B2-C
1x6A 0-15
2x3A 0-15
4x1,5A 0-10
Max. numbers luminaire circuits: 40 A2-3
Terminals:
ACU DG 2,5mm² Rigid/ 1,5mm² flexible A1
Luminaire circuits 4 mm² Rigid/flexible A2-3
Battery feed 16 mm² Rigid/flexible A4
Battery through-wiring 16 mm² Rigid/flexible A4
Mains feed 16 mm² Rigid/flexible A4
Mains through-wiring 16 mm² Rigid/flexible A4
1 2 3 4
A
B
C

Table of Contents