77
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
36 DualGuard-S 28
Technical description Field
Dimensions (W x H x D): 2070 x 800 x 405 mm
Colour: RAL 7035
Weight: 180 kg
Assembly: Only set up on non-combustible ground (e.g. con-
crete).
Degree of protection: IP21, optional IP31, on request IP54
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 400/230 V AC
Rated current (Mains): IN = 80 A
Rated voltage (Battery): 216 V DC
Rated current (Battery): IN =80 A
Rated Frequency: 50 or 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. connected load: At +35°C < 17,3 KW
Maximum numbers of modules: Â1
Controller ACU DG / HMI: 1/1 B1-C1
PSU: 1-2 B2
BCM.1: 1 B3-E
SKU.1.1 CG-S:
1x6A 0-28
2x3A 0-28
4x1,5A 0-20
Luminaire circuits: 0-88 B3
Charger CM 1,7A 1-2 H1-4
Charger CM 3,4A 0-8 F-G
Battery/mains distribution 0-6
Terminals: A2-4
Luminaire circuits: 4 mm² Rigid/flexible A2
BCM.1: 4 mm² Rigid/flexible A1
ACU DG 2,5mm² Rigid/ 1,5mm² flexible F1
Battery feed: 50 mm² Rigid/flexible F2
Battery distribution: 16 mm² Rigid/flexible G1
Mains feed: 50 mm² Rigid/flexible G2
Mains distribution board: 16 mm² Rigid/flexible
Order number accesories:
Cupboard base 100mm 40071362282
Cupboard base 200mm 40071362283
Door hinge left 40071362301
Special locking profile half cylinder 40037079790
IP 31 Retrofit kit 40071362291