87
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
40 DualGuard-S LAD 100
85,7 Ah Battery wiring standing cabinet
89,4 Ah Battery wiring standing cabinet
Technical description
Battery type (C10; 1,8 V/Z; +20 °C): 12 V / 85,7 Ah
Nominal battery voltage of all
switched on cells:
216 V
Numbers of battery blocks: 18 á 12 V
Dimensions per block in mm (L x W x H): 309 x 172 x 239
End poles M8
Order Number battery block: 40066070918
Dimensions per block in mm (L x W x H): 800 x 2050 x 400
Battery consoles: 5
Terminals: max. 35 mm²
Weight incl. Batterys: 685 kg
Degree of protection: IP21
Order Number wiring set: 40071360230
13 x Length 1: 350 mm
4 x Length 2: 800 mm
1 x Length 3: 800 mm
1 x Length 4: 2000 mm
Technical description
Battery type (C10; 1,8 V/Z; +20 °C): 12 V / 89,4 Ahc
Nominal battery voltage of all
switched on cells:
216 V
Numbers of battery blocks: 18 á 12 V
Dimensions per block in mm (L x W x H): 307,5 x 171 x 239
End poles M6
Order Number battery block: 40066070821
Dimensions per block in mm (L x W x H): 800 x 2050 x 400
Battery consoles: 5
Terminals: max. 35 mm²
Weight incl. Batterys: 750 kg
Degree of protection: IP21
Order Number wiring set: 40071360230
13 x Length 1: 350 mm
4 x Length 2: 800 mm
1 x Length 3: 800 mm
1 x Length 4: 2000 mm
1
2
3
4
1. Battery console
2. Battery console
3. Battery console
4. Battery console
5. Battery console
1
2
3
4
1. Battery console
2. Battery console
3. Battery console
4. Battery console
5. Battery console