83
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
30.15 ISA F2M-1 – Manual Reset First Up
30.16 SEQUENCE TABLE
LINE PROCESS
CONDITION
PUSHBUTTON
OPERATION
SEQUENCE
STAT E
VISUAL
DISPLAY
ALARM
AUDIBLE
DEVICE
REMARKS
1 NORMAL NORMAL OFF SILENT
2 FIRST ABNORMAL FIRST ALARM FLASHING AUDIBLE LOCK-IN
3 SUB. ABNORMAL SUB.
ALARM
ON AUDIBLE LOCK-IN
4 FIRST ABNORMAL
OR NORMAL
ACKNOWLEDGE
BEFORE SIL
TO LINE 7 FIRST OUT
RESET
5 SUB. ABNORMAL
OR NORMAL
6 FIRST ABNORMAL
OR NORMAL
SILENCE FIRST
SILENCED
FLASHING SILENT
7 SUB. ABNORMAL
OR NORMAL
SILENCE ACKNOWLEDGE ON SILENT MANUAL
RESET
REQUIRED
8 FIRST ABNORMAL
OR NORMAL
ACKNOWLEDGE
AFTER SILENCE
TO LINE 7 FIRST OUT
RESET
9 NORMAL RESET NORMAL OFF SILENT MANUAL
RESET