84
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
SEQUENCE FEATURES
1. Silence, acknowledge, reset and test pushbuttons
2. Alarm audible device
3. Lock-in of momentary alarms until acknowledged.
4. Option1 – silence pushbutton to silence the alarm audible device while retaining the rst out
ashing indication
5. Flashing indication for rst alarm only. new subsequent alarms have the same visual
indication as acknowledged alarms.
6. First out indication is reset when acknowledged
7. Manual reset of acknowledged alarm indications after process conditions return to normal.
8. Operational test
30.17 ISA F2A-1 – Automatic Reset First Up
This sequence is the same as ISA F2M-1 with the exception that the alarms are automatically reset
once the process has returned to normal.
30.18 ISA F3A – Automatic Reset First Up