I.L.15.01.T.K. Page 15
Effective June 2000
9. Program Setpoints Menu
This table is a guide to the program setpoints menu. An explanation is given for each prompt that
will appear as the Menu Select key is pressed.
Program
Setpoint Display
Setpoint
Possibilities
Display
Explanation
Lang: English, French Language the controller displays messages
Current Day: Mon-Sun Current Day – requires to only be set once
Current Hour: 0-23 Current Hour
Current Min: 0-60 Current Min
Nom.Volt: 110 VAC – 240 VAC
110VAC – 600VAC
System operating voltage
Nom .Freq: 50Hz or 60Hz. System operating frequency
Phases: 1 or 3 Single phase or Three Phase system
TDNE: 0 sec. to 1800 sec. Time Delay Normal to Emergency
TDES: 0 sec. to 120 sec. Time Delay Engine Start
TDEN: 0 sec. to 1800 sec. Time Delay Emergency to Normal
TDEC: 0 sec. to 1800 sec. Time Delay Engine Cooldown
TDN: -none-, N to E, E to N,
global
Time Delay in Neutral position. Can be
selected when transferring in one direction only
or both
TDN: 0 to 120 sec. Time Delay Neutral
TPRE: 0 to 255 sec Pre-Transfer Time Delay
N-UV-DO: 50% to 99% of nominal Source 1 Undervoltage Dropout (% of nominal)
N-UV-PU: (dropout +2%) to 99% Source 1 Undervoltage Pickup (% of nominal)
E-UV-DO: 50% to 99% Source 2 Undervoltage Dropout (% of nominal)
E-UV-PU: (dropout +2%) to 99% Source 2 Undervoltage Pickup (% of nominal)
N-OV-DO: 105% to 120% Source 1 Overvoltage Dropout (% of nominal)
N-OV-PU: (dropout -2%) to 120% Source 1 Overvoltage Pickup (% of nominal)
E-OV-DO: 105% to 120% Source 2 Overvoltage Dropout (% of nominal)
E-OV-PU: (dropout -2%) to 120% Source 2 Overvoltage Pickup (% of nominal)
N-UF-DO: 90% to 99% of nominal Source 1 Underfrequency Dropout (Hz)
N-UF-PU: (dropout +1Hz) – 99% Source 1 Underfrequency Pickup (Hz)
E-UF-DO: 90% to 99% of nominal Source 2 Underfrequency Dropout (Hz)
E-UF-PU: (dropout +1Hz) – 99% Source 2 Underfrequency Pickup (Hz)
N-OF-DO: 103% to 110% Source 1 Overfrequency Dropout (Hz)
N-OF-PU: (dropout –1Hz) – 110% Source 1 Overfrequency Pickup (Hz)
E-OF-DO: 103% to 110% Source 2 Overfrequency Dropout (Hz)
E-OF-PU: (dropout –1Hz) – 110% Source 2 Overfrequency Pickup (Hz)
Pref.Src: enable or disable Preferred source enable or disable
P.S. Select S1, S2 or none Preferred source select. Source 1(Normal),
Source 2(Emergency) or None (source
currently connected)
Man. Retransf. Y or N Pushbutton input for manual return to normal
Test/Area Prot Y or N Test/Area protection enable or disable
Plant Exerciser: Y or N Plant Exerciser enabled or disabled
PE Load Transf: Y or N Plant Exerciser Engine test with or without load
Engine Run: 0 – 600min. Engine run time on exercise
Test Day: --- ,or Mon-Sun Plant Exerciser Day of the week
Test Hour: 0-23 Plant Exerciser Hour
Test Min: 0-60 Plant Exerciser Test Minute
Note: Highlighted options are exclusive to the MP1-E Controller