Page 16 I.L.15.01.T.K.
Effective June 2000
10. Summary of Options
Option
#
Features
Standard/Optional
1 TDNE - Time delay Normal to Emergency Standard
2 TDES - Time delay Engine Start Standard
3 TDEN - Time delay Emergency to Normal Standard
4 TDEC - Time delay Engine Cool-down Standard
5B
1Φ Undervoltage/Underfrequency
Standard
5C
1Φ Overvoltage/Overfrequency
Optional - Programmed
5D
1Φ Undervoltage
Optional - Programmed
5E
1Φ Overvoltage
Optional - Programmed
5F
3Φ Undervoltage
Optional - Programmed
5G
3Φ Overvoltage
Optional - Programmed
5J
3Φ Undervoltage/Underfrequency
Optional – Programmed
5K
3Φ Overvoltage/Overfrequency
Optional – Programmed
6D Maintained 2-Position Test Selector (Auto/Test) Standard - External Contact
6H Maintained 4 –Position Test Selector (Auto/Test/Man./Eng.
Start)
Optional - External Contact
8C Bypass Time Delay Normal to Emergency Optional - External Contact
8D Bypass Time Delay Emergency to Normal Optional - External Contact
8M Bypass Time Delay Global (Both Directions) Optional - External Contact
10 Preferred Source (MP1-E Only) Optional – External Contact
12C Normal Position Standard (On faceplate)
12D Emergency Position Standard (On faceplate)
12G Normal Source Available Standard (On faceplate)
12H Emergency Source Available Standard (On faceplate)
16B Normal Side and Emergency Side Optional - External Contact
16E Emergency Side Only Optional - External Contact
16N Normal Side Only Optional - External Contact
23C No Load Exercise Standard
23D Load Exercise with Failsafe Standard
26A
3Φ Undervoltage
Standard
26B
1Φ Undervoltage
Optional – Programmed
26C
3Φ Overvoltage
Optional – Programmed
26D
1Φ Overvoltage
Optional – Programmed
26E
1Φ Underfrequency
Optional – Programmed
26D Area Protection Optional – External Contact
26F
1Φ Overfrequency Monitor
Optional – Programmed
26H
1Φ Undervoltage / Underfrequency
Optional – Programmed
29J Manual Return to Normal (MP1-E Only) Optional – External Contact
32A Time Delay Neutral Global (Both Directions) Optional – Programmed
32B Time Delay Neutral – (Only on Transfer) Optional – Programmed
32C Time Delay Neutral – (Only on Retransfer) Optional – Programmed
35A Pretransfer (From Norm. to Emerg. Only) (MP1-E Only) Optional - Programmed
35B Pretransfer (From Emergency to Normal) (MP1-E Only) Optional - Programmed
35C Pretransfer (Global – Both Directions) (MP1-E Only) Optional - Programmed