EasyManua.ls Logo

Eaton Cutler-Hammer MP1 Series - 5 Performance Specifications

Eaton Cutler-Hammer MP1 Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.L.15.01.T.K. Page 7
Effective June 2000
5. Performance Specifications
The performance specifications for the ATS-MP1 Controller Board are given in Table 2:
Table 2 – Performance Specifications
Input Control Voltage (50-150)% of V
(IN,RMS)
50/60 Hz
Voltage Measurements of: Normal Source V
AB
Normal Source V
BC
Normal Source V
CA
Emergency Source V
AB
Emergency Source V
BC
Emergency Source V
CA
Voltage Measurement Range: 0 to 360 VAC RMS (50/60Hz) – MP1
0 to 750 VAC RMS (50/60Hz) – MP1-E
Voltage Measurement Accuracy:
± 2% of reading over the monitoring range
Frequency Measurements of: Normal Source (S1), Emergency Source (S2)
Frequency Measurement Range: 40 Hz to 70 Hz
Frequency Measurement Accuracy
± 0.3 Hz over the measurement range
Undervoltage Dropout Range: 50% to 97% of the nominal system voltage
Undervoltage Pickup Range: (Dropout +2%) to 99% of the nominal system voltage
Overvoltage Dropout Range: 105% to 120% of the nominal system voltage
Overvoltage Pickup Range: 103% to (Dropout –2%) of the nominal system voltage
Underfrequency Dropout Range: 90% to 97% of the nominal system frequency
Underfrequency Pickup Range: (Dropout + 1Hz) to 99% of the nominal system frequency
Overfrequency Dropout Range: 103% to 110% of the nominal system frequency
Overfrequency Pickup Range: 101% to (Dropout – 1Hz) of the nominal system frequency
Operating Temperature Range
-20°C to + 70°C
Storage Temperature Range
-35°C to + 85°C
Operating Humidity 0 to 95% relative humidity (non-condensing)
Generator Start Relay 5A, 1/6 HP @ 250VAC
5A @ 30VDC with a 30W maximum load
Alarm Relay 10A, 1-3 HP @ 250VAC
10A @ 30VDC
Table 3 - Applicable Test Standards
UL 991
Canadian Standards Association Conformance (CSA)
UL 1008 / CSA 22.2 No 178.22
Dielectric test
FCC Part 15
Conducted/Radiated Emissions (Class A)
CISPR 11
Conducted/Radiated Emissions (Class A)
IEC 1000-2
Electrostatic Discharge test
IEC 1000-3
Radiated Susceptibility tests
IEC 1000-4
Fast Transient tests
IEC 1000-5
Surge Withstand tests

Related product manuals