I.L. 17403
Page 10
Effective 9/04
Short Circuit Circuit Breaker Short Circuit Withstand Rating Typical
Protective Max. Rating Interrupting Disconnect
Device (SCPD) SCPD Rating Current Voltage Device Cat. No.
100A FD-K
Class J or R 200A - 100,000A 480V Molded Case
Fuse Switch
65,000A 600V
100 & 200A K Sw
Marked GMCP 42,000A 240V GMCP
Magnetic Only
1
60 or 63A 25,000A 480V
Type CB
2
100A Marked HMCP 100,000A 480V HMCP
50,000A 600V
65,000A 65,000A 480V HFD
Thermal/Mag 150A 25,000A 25,000A 600V
Type CB
3
100,000A 100,000A 480V FDC
35,000A 35,000A 600V
Magnetic Only
1
100A HMCP plus 100,000A 600V HMCP + CL
Type CB + CL
4
Current Limiter
Thermal/Mag 150A 100,000A 100,000A 600V HFD + CL
Plus CL
5
600R63A Marked GMCP 42,000A 240V GMCP
Magnetic Only 25,000A 480V
Type CB
2
100A Marked HMCP 100,000A 480V HMCP
50,000A 600V
100A Marked HMCPE 100,000A 480V HMCPE
TABLE VI - SIZE 3 SHORT CIRCUIT RATINGS
TABLE NOTES
1
Instantaneous Adjustable Trip
2
Circuit Breaker
3
Inverse Time Circuit Breaker
4
Instantaneous Adjustable Trip Circuit Breaker with Current-Limiting
Attachment
5
Inverse Time Circuit Breaker with Current-Limiting Attachment
SHORT CIRCUIT RATINGS
These motor controllers are suitable for use on circuits
capable of delivering not more than the current (rms sym-
metrical amperes) shown, in circuits rated not more than
the voltage shown in Tables VI and VII when protected
by the SCPD shown.