EasyManua.ls Logo

Eaton Cutler-Hammer W200 - TWO-WIRE CONTROL WIRING; Two-Wire Control Setup; Two-Wire Control With IMPACC; Automatic Reset Warning

Eaton Cutler-Hammer W200
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.L. 17403
Page 9
Effective 9/04
Interposing Relay
START
STOP
3
2
LOW VOLTAGE RELEASE WITH
TWO-WIRE PUSHBUTTON
START-STOP OPERATION
Fig. 11 Two-Wire Control
Fig. 12 Two-Wire Control with IMPACC
TWO-WIRE CONTROL
Wire as shown in Figure 11 or 12. Install a #16 or #18
AWG stranded wire jumper from 3 to P. Keep strip length
to not more than 1/4 inch. Be sure to have jumper clear
power terminal. Attach and route twisted pair or shielded
wires to a remote reset/trip indicator module where pro-
vided.
Without Communications
Wire control devices in the same manner as conventional
motor controllers. Add the jumper.
With Communications
Attach a WPONI communications module and connect it
to the INCOM network daisy-chain fashion as shown in
Figures 4 and 12.
When wired as shown in Figure 12 with two-wire control,
the motor cannot be started or stopped via IMPACC. The
motor starter can only be reset and data obtained via
IMPACC where two-wire control is used.
Automatic reset should not be used with two-wire
control circuit where automatic starting of the motor
may be hazardous.
3C
GENERIC
PILOT
CIRCUIT
(PLC)
RELAY
P and/or
P
5300C76D
5300C76C

Related product manuals