EasyManua.ls Logo

Eaton ELC-PB - Page 87

Eaton ELC-PB
728 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ELC Programming Manual
FOR MORE INFORMATION VISIT: WWW.EATON.COM MN05003003E
2-58
Special D
Function
ELC
-PB
ELCB
-PB
ELC
-PC
-PA
-PH
ELCM
-PH
- PA
ELC
-PV
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Type Latched
Factory
setting
D1062
For ELC-PA controllers, sampling
range of AD (CH0, CH1): 2~4
- Y - - - 2 - R/W NO 2
D1063
For ELCM-PA controllers: sampling
range of AD0AD3 (CH0~CH3)):1~20
- - Y -
D1064
ELC flash ROM access function for
program, password and data.
ELC reads flash: H55AA
ELC writes flash: HAA55
- - - Y 0 - - R/W NO 0
D1067
Algorithm error code
Y Y Y Y 0 0 - R NO 0
D1068
Lock the algorithm error address
Y Y Y Y 0 - - R NO 0
D1070
D1085
When the ELC’s built-in RS-485
communication instruction receives
feedback signals from receiver. The
data will be saved in the registers
D1070~D1085. User can use the
contents saved in the registers to
check the feedback data.
Y Y Y Y 0 - - R NO 0
D1086
ELC-ACPGMXFR
High word of password setting (Display
by HEX value corresponding to ASCII
word)
Y Y Y Y 0 - - R/W NO 0
D1087
ELC-ACPGMXFR
Low word of password setting (Display
by HEX value corresponding to ASCII
word)
Y Y Y Y 0 - - R/W NO 0
D1089
D1099
When the ELC built-in RS-485
communication instruction is executed,
the transmitting signals will be stored
in the registers D1089~D1099. User
can use the contents saved in
registers to check the feedback data.
Y Y Y Y 0 - - R NO 0
D1100
Corresponding status after LV signal is
enabled
- - - Y 0 - - R/W NO 0
D1101
Start address of file register
- Y - Y - - - R/W Yes 0
D1102
Copy numbers of file register
- Y - Y - - - R/W Yes 1600
D1103
Set start D number for file register to
store (the number should be large than
2000)
- Y - Y - - - R/W Yes 2000
D1104
Parameter index for Accel/Decel pulse
output Y0 (corresponds to device D)
Y Y - - 0 0 - R/W NO 0
D1109
COM3 (RS-485) Communication
protocol
- - Y - 0086 - - R/W NO 0086