2. Programming Concepts
MN05003003E For more information visit: www.eaton.com
2-59
Special D
Function
ELC
-PB
ELCB
-PB
ELC
-PC
-PA
-PH
ELCM
-PH
- PA
ELC
-PV
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Type Latched
Factory
setting
Average of PA controller analog input
channel 0 (CH 0)
- Y - -
D1110
Average of ELCM-PA analog input
CH0 (AD 0) When sampling range in
D1062 is set to 1, D1110 indicates
present value.
- - Y -
0 - - R NO 0
Average of PA controller analog input
channel 1 (CH 1)
- Y - -
D1111
Average of ELCM-PA analog input
CH1 (AD 1) When sampling range in
D1062 is set to 1, D1110 indicates
present value
- - Y -
0 - - R NO 0
D1112
Average value of ELCM-PA analog
input CH2
- - Y -
0 - - R NO 0
D1113
Average value of ELCM-PA analog
input CH3
- - Y -
0 - - R NO 0
D1114
For ELCM-PA controllers: enable /
disable input channel setting of
AD0~AD3 by bit 0~bit 3. (0:
enable(default), 1: disable)
- - Y -
- - - R/W NO 0
D1115
Analog mode selection (0 : Voltage / 1:
Current)
bit0~bit3 refer to AD0~AD3,
bit4~bit5 refer to DA0~DA1
bit8~bit13: current mode selection
bit8~ bit11 refer to AD0~AD3,
(0: -20mA~20mA, 1: 4~20mA)
bit12, bit13 refer to DA0~DA1,
(0: 0~20mA, 1: 4~20mA)
- - Y -
0 0 0 R/W NO 0
D1116
PA controller analog output channel 0
(CH 0)
- Y Y - 0 0 0 R/W NO 0
D1117
PA controller analog output channel 1
(CH 1)
- Y Y - 0 0 0 R/W NO 0
ELC-PA controller only. Sampling time
of analog/digital conversion. Default: 5.
Unit: 1ms. Sampling time will be
regarded as 5ms if D1118≦5
- Y - - 5 - - R/W NO 5
D1118
For ELCM-PA only. Sampling time of
analog/digital conversion. Default: 2.
Unit: 1ms. Sampling time will be
regarded as 2ms if D1118≦2
- - Y - 2 - - R/W NO 2
D1120
COM2 (RS-485) communication
protocol
Y Y Y Y 0086 - - R/W NO 0086
ELC communication address (the
address that save the ELC
communication address)
Y Y - Y
D1121
COM1(RS-232) and COM2(RS-485)
the ELC communication address
- - Y -
- - - R/W Yes 1
D1122
Residual words of transmitting data
Y Y Y Y 0 0 - R NO 0