12
Programming
EPCT FIRE SERIES FIRE PUMP CONTROLLER MN124016EN August 2019 www.eaton.com
Description Range
Fail to Stop Timer 0-999 seconds / Disabled
Weekly motor
test timer
Enabled / Disabled
Day of the Week Any valid day of the week
Time of Day 24 Hours
Test Interval 1-52 weeks
Run Time Four (4) digit numeric entry in Minutes:
Seconds / Disabled
Drain Valve Solenoid Enabled / Disabled
ATS settings (if equipped)
Time Delay S1 to S2 Three (3) digit numeric entry in Minutes:
Seconds / Disabled
Time Delay S2 to S1 Three (3) digit numeric entry in Minutes:
Seconds / Disabled
Time Delay Neutral Three (3) digit numeric entry in Minutes:
Seconds / Disabled
Time Delay Engine Start Three (3) digit numeric entry in Minutes:
Seconds / Disabled
Time Delay S2 Fail 0-9 seconds / Disabled
Time Delay Engine Cooldown Three (3) digit numeric entry in Minutes:
Seconds / Disabled
Dual utility
Enabled / Disabled
Preferred Source Source 1 / Source 2
Weekly engine
test timer
Enabled / Disabled
Day of the Week Monday / Tuesday / Wednesday / Thursday /
Friday / Saturday / Sunday
Time of Day 24 Hours
Test Interval 1-52 weeks
Run Time Four (4) digit numeric entry in Minutes:
Seconds / Disabled
Transfer Load Enabled / Disabled
Alarm setpoints
Phase Rotation ABC / CBA / Disabled
Phase Failure Alarm
Setpoint
0-100% / Disabled
Motor Overlead Setpoint 100-999%
Transducer Fail Pump Start Enabled / Disabled
Abort Motor Test on Low
Voltage
Enabled / Disabled
Voltage alarm settings
Source 1 Under Voltage 0-100% / Disabled (Dropout)
0-100% / Disabled (Pickup)
Source 1 Over Voltage 100-999% / Disabled (Dropout)
100-999% / Disabled (Pickup)
Source 2 Under Voltage 0-100% / Disabled (Dropout)
0-100% / Disabled (Pickup)
Source 2 Over Voltage 100-999% / Disabled (Dropout)
100-999% / Disabled (Pickup)
Frequency alarm settings
Source 1 Under Frequency 0-100% / Disabled (Dropout)
0-100% / Disabled (Pickup)
Source 1 Over Frequency 100-999% / Disabled (Dropout)
100-999% / Disabled (Pickup)
Source 2 Under Frequency 0-100% / Disabled (Dropout)
0-100% / Disabled (Pickup)
Description Range
Source 2 Over Frequency 100-999% / Disabled (Dropout)
100-999% / Disabled (Pickup)
Inputs/outputs
Input 1 See Table 2
Input 2 See Table 2
Input 3 See Table 2
Input 4 See Table 2
Input 5 See Table 2
Input 6 See Table 2
Input 7 See Table 2
Input 8 See Table 2
Input 9 See Table 2
Input 10 See Table 2
Input On Delay Timer 0-999 seconds / Disabled
Input Off Delay Timer 0-999 seconds / Disabled
Latch Until Reset Enabled / Disabled
Failsafe Enabled / Disabled
3CR Relay See Table 3
4CR Relay See Table 3
5CR Relay See Table 3
6CR Relay See Table 3
Pressure Above 0-999 PSI / Disabled
Pressure Below 0-999 PSI / Disabled
Load Shed Controller
Start Delay
0-10 seconds / Disabled
Relay On Delay Timer 0-999 seconds / Disabled
Relay Off Delay Timer 0-999 seconds / Disabled
Latch Until Reset Enabled / Disabled
Failsafe Enabled / Disabled
5.3 Startup tab
Refer to Appendix B for the menu structure of the Startup tab.
5.3.1 Quick setup
Quick Setup is a step-by-step process that allows the user
to program the time, day of the week, date, start pressure,
stop pressure, automatic shutdown, and minimum run time
(if automatic shutdown was enabled). If all settings are
correct, the user will press Accept to save the changes.
5.3.2 Setup phase reversal
Guides the user through a step-by-step process to verify
that the motor is or is not spinning in the correct direction.
Pressing “Motor Bump” will start a five (5) second
countdown timer and, once elapsed, will bump the motor for
a period of one (1) second. If spinning correctly, the controller
will save the phase reversal setpoint into the programming. If
the motor is not spinning correctly, the controller will provide
a prompt on the necessary changes required.
For controllers equipped with an ATS, the sequence will
continue. Pressing the “Start Generator/Transfer” will
initiate a call-to-start on the generator and, once voltage
is available on the Source 2 input, the ATS will transfer to