S
Shannon HenrySep 12, 2025
Why is the Eaton UPS load no longer supplied when the rotary switch on the HotSwap MBP module is set to the Bypass position?
- JJessica CarrSep 12, 2025
If the Eaton UPS load is not supplied when the rotary switch on the HotSwap MBP module is in the Bypass position, the protected devices may be incorrectly wired to the UPS output instead of the HotSwap MBP module. Alternatively, the AC power cord may be connected to the UPS input instead of the HotSwap MBP module. Check the wiring between the UPS and the HotSwap MBP module.







