What to do if the Eaton EX 700 load is no longer supplied if AC power fails?
- CCaitlyn CowanJul 31, 2025
If the Eaton UPS load is no longer supplied during an AC power failure, ensure that the rotary switch on the HotSwap MBP module is set to the Normal position. Also, verify the wiring between the UPS and the HotSwap MBP module.