Installation
20
11/01 AWB2300-1433GB
The following conductor cross-sections can be used.
Table 5: Maximum conductor cross-sections of the motor
cables
Mounting for low motor currents
At the ZEV-XSW-25, the cables for motors operating with a
current < 1 A are looped. The number of loops is determined
by the rated operational current of the motor I
N
(a table 6).
Figure 10: Loops of the motor feed cables
Table 6: Number of loops
I
N
= rated operational current of the motor
I
e
= current setting at the ZEV
Current sensor
Feedthrough
O
Conductor cross-section
mm mm
2
AWG
ZEV-XSW-25 6 10 solid or multi-wire 10
ZEV-XSW-65 13 50 fine-wire 1
ZEV-XSW-145 21 150 fine-wire 2/0
I
II
I
N
[A]
0.25 to 0.4 0.41 to 0.62 0.63 to 1.24
Number of
loops
4 3 2
I
e
4 x (0.25 to 0.4) 3 x (0.41 to 0.62) 2 x (0.63 to 1.24)