IM02602002E
www.eaton.com Page 4-3
MP-3000

Trip
Auxiliary 1
Alarm
Auxiliary 2
Program
Monitor
View Setting
Protection
Log
History Mode
Protection
Aux 1
Page
Prog
Over
ride
Emrg
Line Value
Monitor
Program
View Setting History
Aux 2
Trip
Alarm
Log
Help
Reset
MP-3000

  
READY--1 READY TO START MOTOR, SINGLE
PHASE TEST MODE

MP-3000 has been set to 1 PHASE for bench testing only. Will not
protect a 3-phase motor. Change setting P13L1 to 3 PHASE for
normal motor protection.
READY--3 READY TO START MOTOR, THREE
PHASE TEST MODE
Motor is stopped and MP-3000 is ready for a start, 3-phase mode.
RUN MOTOR IS RUNNING Motor is running, as indicated by phase currents.
START ATTEMPTING TO START MOTOR Motor is starting, and has not yet reached transition to RUN as
dened by User settings.
DISARMED WARNING RELAY IS DISARMED
AND CAN NOT TRIP

Protection functions have been blocked from operating the trip relay
by User setting P12L18. MOTOR IS UNPROTECTED. This mode
of operation is for commissioning in a critical process only. Refer to
Section 5.12.18.
ABKSP XX ANTI-BACKSPIN ACTIVE, REMAIN-
ING MINUTES ACTIVE SHOWN
The motor is stopped, and the trip contact has been opened to pre-
vent restarting until the antibackspin time delay has expired. XX is
the remaining minutes before restarting is allowed.
ILLEGAL AN ILLEGAL REQUEST WAS MADE Response to request for an action that the relay cannot perform.
Setpoints were not properly stored. Reprogram the unit and save
settings.