IM02602002E
Page 4-4
www.eaton.com
MP-3000

SUB-
MENU
LINE DISPLAY COMPLETE HELP MESSAGE DESCRIPTION
MONITOR REAL-TIME VALUES Monitor mode
MONT I REAL-TIME DATA FROM CURRENT MEASUREMENTS Current monitoring data follows
1 IAV XXX AVERAGE CURRENT OF THE THREE PHASES Average RMS current of 3-phase currents in amps
2 IA XXX PHASE A CURRENT IN AMPS Actual ac line motor RMS current
3 IB XXX PHASE B CURRENT IN AMPS Actual ac line motor RMS current
4 IC XXX PHASE C CURRENT IN AMPS Actual ac line motor RMS current
5 IG XXX GROUND FAULT CURRENT IN AMPS Actual ground current
6 %IA XXX PHASE A CURRENT AS A PERCENT OF FULL LOAD AMPS Percentage of actual monitored current in amps
7 %IB XXX PHASE B CURRENT AS A PERCENT OF FULL LOAD AMPS Percentage of actual monitored current in amps
8 %IC XXX PHASE C CURRENT AS A PERCENT OF FULL LOAD AMPS Percentage of actual monitored current in amps
9 %UB XXX PHASE UNBALANCE - IF POSITIVE THE RATIO OF NEGATIVE
TO POSITIVE SEQUENCE CURRENT - IF NEGATIVE THE
INVERSE
Ratio of negative sequence current to positive
sequence current in percent. If a phase reversal
exists, the ratio is inverted and a negative sign is displayed.
MONT
RTD
REAL-TIME DATA FROM RTD MODULE RTD monitoring data follows. (Page only visible
when URTD communicates with MP-3000.)
1 WT1 XXX WINDING TEMP 1 IN DEGREES F or C RTD reading - terminals 1, 2, 3
2 WT2 XXX WINDING TEMP 2 IN DEGREES F or C RTD reading - terminals 4, 5, 6
3 WT3 XXX WINDING TEMP 3 IN DEGREES F or C RTD reading - terminals 7, 8, 9
4 WT4 XXX WINDING TEMP 4 IN DEGREES F or C RTD reading - terminals 10, 11, 12
5 WT5 XXX WINDING TEMP 5 IN DEGREES F or C RTD reading - terminals 13, 14, 15
6 WT6 XXX WINDING TEMP 6 IN DEGREES F or C RTD reading - terminals 17, 18, 19
7 MT1 XXXX MOTOR BEARING TEMP 1 IN DEGREES
F or C
RTD reading - terminals 20, 21, 22
8 MT2 XXXX MOTOR BEARING TEMP 2 IN DEGREES
F or C
RTD reading - terminals 23, 24, 25
9 LT1 XXXX LOAD BEARING TEMP 1 IN DEGREES
F or C
RTD reading - terminals 26, 27, 28
10 LT2 XXXX LOAD BEARING TEMP 2 IN DEGREES
F or C
RTD reading - terminals 29, 30, 31
11 AXT XXXX AUXILIARY TEMP IN DEGREES F or C RTD reading - terminals 33, 34, 35
MONT
MTR
REAL-TIME MOTOR DATA Motor monitoring data follows
1 VER XXXX SOFTWARE VERSION NUMBER MP-3000 software version in use
2 %I2T XXX PERCENT OF I2T TRIP LEVEL Percentage of thermal bucket used
3 TUS XXX TIME IN MINUTES UNTIL NEXT START CAN OCCUR Displays largest amount of time in minutes among
three functions: anti-backspin, starts per unit time
and time between starts
4 RMST XX REMAINING STARTS Number of starts remaining if starts per time is programmed
5 OST XXX TIME LEFT ON OLDEST START IN MINUTES Remaining time allowed on oldest start for starts per time if
programmed. If motor start/time is exceeded, this is time in minutes
before restart is permitted.
6 ICM XXXX ADDRESS ON THE IMPACC NETWORK IN HEXADECIMAL Address of device if on INCOM communications network; only visible
if on network
7 DI 1 OFF or
DI 1 ON
STATE OF DISCRETE INPUT 1 Current state of discrete input 1; ON = 120 VAC present, OFF = 120
VAC not present
8 DI 2 OFF or
DI 2 ON
STATE OF DISCRETE INPUT 2 Current state of discrete input 2; ON = 120 VAC present, OFF = 120
VAC not present
MONT
TIM
DATE AND TIME Current date and time with display format as programmed
1 HH.MM XM CURRENT TIME 12-hour format
or or
HH.MM 24-hour format
2 MM/DD/YY CURRENT DATE Common format
or or