IM02602002E
www.eaton.com Page 4-9
MP-3000
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
VALUE SELECTED
8 INSQ XXX INCOMPLETE SEQUENCE REPORT
BACK TIME IN SECONDS ON DISCRETE
INPUT 2
1-240 sec., OFF (1 sec. increments)
NOTE: Choosing a time value here (not OFF)
also locks P7L1 to INC SEQ and no other choices
are available there. Also, if this is set to OFF, a
later setting of P7L1 to INC SEQ will force a
setting of here.
9 INSQ TRN
or
INSQ ST
INCOMPLETE SEQUENCE START TIME
EVENT INSQ TRN - START TO RUN
TRANSITION INSQ ST - STOP TO START
TRANSITION
Toggles between INSQ TRN and
10 LAT XXX LONG ACCELERATION TIME IN
SECONDS
1-200 sec., (1 sec. increments)
- Set to OFF unless absolutely needed.
If used, connect zero-speed switch. Refer to
settings P5L11 and P6L1.
11 ZSW ON
or
ZSW OFF
ZERO SPEED SWITCH ON DISCRETE
INPUT 1 ON OR OFF
Toggles between ZSW ON and .
NOTE: Choosing ZSW ON here also locks
P6L1 to ZERO SW and no other choices are
available there. Also, setting P6L1 to ZERO SW
will force ZSW ON here.
12 ABK XXXX ANTI-BACKSPIN DELAY TIME IN
SECONDS
1-3,600 seconds, (1 sec. increments)
1 Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
ZERO SW
EMG OVR
CONFIGURE DISCRETE
INPUT 1 --
REM RESET - REMOTE RESET
REM TRIP - REMOTE TRIP
DIF TRIP - DIFFERENTIAL TRIP
MTR STOP - MOTOR STOP DETECTION
RST DBL - RESET DISABLE
ZERO SW - ZERO SPEED SWITCH TO
GET ANY OTHER
EMG OVR - EMERGENCY OVERRIDE
Choose from the seven selections for the function
of Discrete Input 1.
If ZERO SW is selected here, P5L11 will
be forced to ZSW ON.
If P5L11 was already set to ZSW ON,
this setting is automatically set to ZERO.
SW and no other selections are visible.
1 Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
INC SEQ
EMG OVR
CONFIGURE DISCRETE INPUT 2 --
REM RST - REMOTE RESET
REM TRIP - REMOTE TRIP
DIF TRIP - DIFFERENTIAL TRIP
MTR STOP - MOTOR STOP DETECTION
RST DBL - RESET DISABLE
INC SEQ - INCOMPLETE SEQUENCE
EMG OVR - EMERGENCY OVERRIDE
Choose from the seven selections for the function
of Discrete Input 2.
If is selected here, P5L8 will be
turned on and set to 1 second.
If P5L8 was already set to a time value (not OFF),
this setting is automatically set to INC SEQ
and no other selections are visible.
1 Choose:
GF A ON
GFT ON
or
GF OFF
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , GF T ON, and
GF T OFF
2 Choose:
I2T A ON
I2T T ON
or
12T OFF
ENABLE I2T ALARM OR TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
Toggles between , I2T T ON, and
I2T OFF
3 Choose:
JAM A ON
JAM T ON
or
JAM OFF
ENABLE JAM ALARM OR TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
Toggles between , JAM T ON, and
JAM OFF
4 Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDER LOAD ALARM OR TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between , UL T ON, and
UL OFF