IM02602002E
Page 4-10
www.eaton.com
MP-3000

SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE


VALUE SELECTED
5 Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , UB T ON, and
UB OFF

6 Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , WD T ON, and
WD OFF
7 Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , MB T ON, and
MB OFF
8 Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , LB T ON, and
LB OFF
9 Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , AX T ON, and
AX OFF
10 Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between , SX T on, and
SX OFF
11 Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between TBS T ON and 
12 RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between  and RTDF OFF
13 RCOM ON
or
RCOM OFF
ENABLE RTD MODULE
COMMUNICATION FAILURE TO
ACTIVATE ALARM RELAY OR DISABLE
Toggles between  and RCOM OFF
14 IOCT ON
or
IOCT OFF
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between IOCT ON and 
15 PH R ON
or
PH R OFF
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
Toggles between PH R ON and 
16 INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between INSQ ON and 
17 REMT ON
or
REMT OFF
ENABLE REMOTE TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between REMT ON and 
18 DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between DIFT ON and 
19 INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between INCT ON and 
20 TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between TRNT ON and 
21 ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between ZSWT ON and 
22 TBYP ON
or
TBYB OFF
ENABLE TRIP BYPASS TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between TBYP ON and 