IM02602002E
www.eaton.com Page 4-11
MP-3000

SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE


VALUE SELECTED

1 LSPU XXX LOAD SHED PICK-UP CURRENT AS
% OF FLA
50-150%,  (1% increments)
NOTE: P9L1 and P9L2 are forced to be
coherent. Refer to Section 5 for details.
2 LSDO XXX LOAD SHED DROP-OUT CURRENT AS
% OF FLA
50-LSPU Value %,  (1% increments)
NOTE: P9L1 and P9L2 are forced to be
coherent. Refer to Section 5 for details..
3 LSDL XX LOAD SHED DELAY IN SECONDS 0-5 sec. (0.1 sec. increments)
If LSPU and LSDO are both set to OFF, the
following SP AUX1 functions are available and
visible. 
4 Choose:
GF A ON
GFT ON
or
GF OFF
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between GF A ON, GF T ON, and

5 Choose:
I2T A ON
I2T T ON
or
I2T OFF
ENABLE I2T ALARM OR TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between I2T A ON, , and
I2T OFF
6 Choose:
JAM A ON
JAM T ON
or
JAM OFF
ENABLE JAM ALARM OR TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between JAM A ON, JAM T ON, and

7 Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDERLOAD ALARM OR TRIP
TO ACTIVATE AUX1 RELAY OUTPUT
OR DISABLE
Toggles between UL A ON, UL T ON, and 

8 Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between UB A ON, UB T ON, and

9 Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between WD A ON, WD T ON, and

10 Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between MB A ON, MB T ON, and

11 Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between LB A ON, LB T ON, and

12 Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between AX A ON, AX T ON, and

13 Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between SX A ON, SX T ON, and

14 Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between TBS T ON and 
15 RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between RTDF ON and 