IM02602002E
Page 4-12
www.eaton.com
MP-3000
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
VALUE SELECTED
16 RCOM ON
or
RCOM OFF
ENABLE RTD MODULE
COMMUNICATION FAILURE TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between RCOM ON and
17 IOCT ON
or
IOCT OFF
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between IOCT ON and
18 PH R ON
or
PH R OFF
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between PH R ON and
19 INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between INSQ ON and
20 REMT ON
or
REMT OFF
ENABLE REMOTE TRIP TO ACTIVATE
AUX1 RELAY OUTPUT OR DISABLE
Toggles between REMT ON and
21 DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between DIFT ON and
22 INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO ACTIVATE
AUX1 RELAY OUTPUT OR DISABLE
Toggles between INCT ON and
23 TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between TRNT ON and
24 ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE AUX1 RELAY OUTPUT
OR DISABLE
Toggles between ZSWT ON and
25 TBYP ON
or
TBYP OFF
ENABLE TRIP BYPASS TO ACTIVATE
AUX1 RELAY OUTPUT OR DISABLE
Toggles between TBYP ON and
1 TRN ON
or
TRN OFF
ENABLE TRANSITION OUTPUT IF
ENABLED ALL OTHER FUNCTIONS
FOR AUX 2 ARE DISABLED
Toggles between and TRN OFF.
If TRN is set to OFF then the following SP AUX2
functions are available and visible.
2 Choose:
GF A ON
GF T ON
or
GF OFF
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE AUX 2 RELAY
OUTPUT OR DISABLE
Toggles between GF A ON, GF T ON, and
3 Choose:
I2T A ON
I2T T ON
or
V
ENABLE I2T ALARM OR TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between I2T A ON, I2T T ON, and
4 Choose:
JAM A ON
JAM T ON
or
JAM OFF
ENABLE JAM ALARM OR TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between JAM A ON, JAM T ON, and
5 Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDERLOAD ALARM OR TRIP
TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
Toggles between UL A ON, UL T ON, and
6 Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UB A ON, UB T ON, and
7 Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between WD A ON, WD T ON, and