IM02602002E
www.eaton.com Page 4-13
MP-3000
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
VALUE SELECTED
8 Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between MB A ON, MB T ON, and
9 Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between LB A ON, LB T ON, and
10 Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between AX A ON, AX T ON, and
11 Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between SX A ON, SX T ON, and
12 Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
Toggles between TBS T ON and
13 RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between RTDF ON and
14 RCOM ON
or
RCOM OFF
ENABLE RTD MODULE
COMMUNICATION
FAILURE TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between RCOM ON and
15 IOC A ON
IOC T ON
or
IOC OFF
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between IOCT ON and
16 PH R ON
or
PH R OFF
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between PH R ON and
17 INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between INSQ ON and
18 REMT ON
or
REMT OFF
ENABLE REMOTE TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
Toggles between REMT ON and
19 DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between DIFT ON and
20 INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
Toggles between INCT ON and
21 TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between TRNT ON and
22 ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED SWITCH TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
Toggles between ZSWT ON and
23 TBYP ON
or
TBYP OFF
ENABLE TRIP BYPASS TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
Toggles between TBYP ON and
1 MAX 100 4-20 MA OUTPUT
Select one of MAX 100, , MAX
WRTD or MAX %I2T
MAX 125 MAX 100-20 MA FOR 100% FLA
MAX WRTD MAX 125-20 MA FOR 125% FLA
MAX %I2T MAX WRTD - 20 MA FOR TRIP LEVEL
MAX %I2T-20MA FOR 100% I2T