IM02602002E
Page 4-14
www.eaton.com
MP-3000
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
VALUE SELECTED
1 TP MODE X CONFIGURE TRIP RELAY OUTPUT TO
BE MODE 1 --
TRIP RELAY ENERGIZES ON TRIP
EVENT OR MODE 2 --TRIP RELAY
ENERGIZES ON POWER UP AND
DE-ENERGIZES ON TRIP EVENT
Toggles between TP MODE 1 and
2 AL MODE X CONFIGURE ALARM RELAY OUTPUT
TO BE MODE 1 - ALARM RELAY
ENERGIZES ON ALARM EVENT OR
MODE 2 - ALARM RELAY ENERGIZES
ON POWER UP AND DE-ENERGIZES
ON ALARM EVENT
Toggles between AL MODE1 and
3 AX1 MOD X CONFIGURE AUX1 RELAY OUTPUT TO
BE MODE 1 - AUX1 RELAY ENERGIZES
ON AUX1 EVENT OR MODE 2 - AUX1
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX1 EVENT
Toggles between and AX1 MOD2
4 AX2 MOD X CONFIGURE AUX2 RELAY OUTPUT TO
BE MODE 1 - AUX2 RELAY ENERGIZES
ON AUX2 EVENT OR MODE 2 - AUX2
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX2 EVENT
Toggles between and AX2 MOD2
5 MAN I2T
or
AUTO I2T
AUTO OR MANUAL I2T RESET
Toggles between and AUTO I2T
6 RUN PGM
or
STOP PGM
ENABLE UNIT TO BE PROGRAMMED
WHILE MOTOR IS RUNNING
Toggles between RUN PGM and
7 EMRG EN
or
EMRG DIS
EMERGENCY OVERRIDE ENABLE
EMRG EN - ENABLE EMERGENCY
OVERRIDE
EMRG DIS - DISABLE EMERGENCY
OVERRIDE
Toggles between EMRG EN and
8 12 HOUR
or
24 HOUR
SET MONITOR MODE CLOCK DISPLAY
12 HOUR - AM/PM TIME DISPLAYED
24 HOUR - 24 HOUR TIME DISPLAYED
Toggles between and 24 HOUR
9
M D Y
D M Y
SET REAL TIME DATE DISPLAY -
MONTH DAY YEAR OR
DAY MONTH YEAR
or D M Y
10 IQ2 DIS INCOM COMMUNICATIONS MODE
Toggles between and EN
IQ2 EN -IQ1000II EMULATION
IQ2 DIS - MP3000 COMMUNICATION
11 RLYF TRP
RLYF ALM
or
RLYF T+A
INTERNAL DIAGNOSTIC FAILURE
ACTIVATES TRIP AND OR ALARM
RELAY
Toggles between RLYF TRP, RLYF ALM and
12 INCT DIS
or
INCT EN
INCOM TRIP DISABLED OR ENABLED
Toggles between INCT DIS and
13 DISARMED
or
ARMED
ARM OR DISARM TRIP RELAY
WARNING DISARM WILL NOT ALLOW
TRIP RELAY TO FUNCTION
Toggles between and DISARMED
1 3 PHASE
or
1 PHASE
SINGLE PHASE TEST MODE OR
THREE PHASE PROTECTION MODE
Toggles between and 1-PHASE
NOTE: 1-PHASE is for bench testing ONLY.
2 TRP ENER
or
TRP DENR
TRP ENER - ENERGIZE TRIP RELAY
TRP DENR - DE-ENERGIZE TRIP RELAY
Toggles between TRP ENER and TRP DENR
Press and hold Reset button to perform
selected test
3 ALM ENER
or
ALM DENR
ALM ENER - ENERGIZE ALARM RELAY
ALM DENR - DE-ENERGIZE ALARM
RELAY
Toggles between ALM ENER AND ALM DENR
Press and hold Reset button to perform
selected test