IM02602002E
www.eaton.com Page 12-7
MP-3000

1. Setting P12L16 permits a choice as to whether these internal failures produce alarm plus trip, or just an alarm.

 Probable Cause Solution
All LEDs and displays are off or
unintelligible.
Incoming ac decient
MP-3000 malfunctioning
The MP-3000 operates down to 55% of
rated voltage, but such a low voltage is
not normal and should be diagnosed.
Verify that 120 or 240 Vac (±15%) exists
between terminals 4 and 7.
Remove ac power completely for 10
seconds and reapply it. If the problem
persists, return the MP-3000 to the
factory for repair.
OPTO ERR message An optocoupler failure trip based on bad
timing of ac input waveform zero cross-
ings
Check the frequency setting P1L7 for
50 or 60 Hz, as appropriate. Make sure
120 Vac is used for discrete inputs.
Energizing with dc causes this error
message.

1
.
  
A/D ERR A/D CONVERTER ERROR TRIP Reset unit. If problem persists, replace unit.
RAM ERR RAM ERROR TRIP
Cycle control power. If problem persists, reprogram unit,
save settings, and cycle control power. If problem still
persists, replace unit.
ROM ERR ROM ERROR TRIP Replace unit or contact Eaton.
OPTO ERR OPTOCOUPLER FAILURE TRIP Refer to Table 12.3, OPTO ERR, for details.
ZRAM ERR
NON VOLATILE MEMORY
ELEMENT SHOULD BE REPLACED
Cycle power. If problem persists, reprogram unit, save set-
tings, and cycle control power. If problem still persists, unit
needs recalibration. Contact the Eaton supplier.
FLASHERR FLASH WRITING ERROR
Reprogram settings and cycle control power. If problem
persists, replace unit or contact Eaton.