4. Complementary features
POWER XPERT® RELEASE TRIP UNIT FOR MAGNUM PXR CIRCUIT BREAKERS   MN013015EN   January 2022   www.eaton.com
Table 8.  Configurable relay functions (continued).
Condition/function 
name
Description of relay operation:
The relay will close 
when … 
The relay will open 
when … 
Internal alarm There is an internal fault 
detected
RESET button is pressed 
or communications reset 
command received
Health warning
(relay #1 default non-
ARMS styles)
Health value is below 
setpoint (adjustable from 
10 to 50%)
Health value is at or 
above setpoint
Communication alarm Any external 
communications error 
occurs 
RESET button is pressed 
or communications reset 
command received
Alarm present  Any of the internal, 
health, communication, 
or battery alarms are 
active
All of the referenced 
faults are inactive
Over voltage Voltage is greater than 
or equal to setpoints for 
pickup and time (ANSI 
59)
If set as alarm: voltage is 
less than pickup;
If set as TRIP: RESET 
pressed or reset 
command received.
Under voltage Voltage is less than or 
equal to setpoints for 
pickup and time (ANSI 
27)
If set as ALARM: voltage 
is greater than pickup;
If set as TRIP: RESET 
pressed or reset 
command received.
Voltage unbalance Voltage unbalance is 
greater than or equal to 
setpoints for pickup and 
time (ANSI 47)
If set as ALARM: voltage 
unbalance is less than 
pickup;
If set as TRIP: RESET 
pressed or reset 
command received.
Current unbalance Current unbalance is 
greater than or equal to 
setpoints for pickup and 
time (ANSI 46)
If set as ALARM: current 
unbalance is less than 
pickup;
If set as TRIP: RESET 
pressed or reset 
command received.
Reverse active power Reverse active power is 
greater than or equal to 
setpoints for pickup and 
time (ANSI 32R)
If set as ALARM: reverse 
active power is less than 
pickup;
If set as TRIP: RESET 
pressed or reset 
command received.
Over power demand Real power demand is 
greater than or equal 
to setpoints for pickup 
and time 
If set for ALARM: real 
power demand is less 
than pickup;
If set as TRIP: RESET 
pressed or reset 
command received.
Phase loss (current) At least one phase is 
less than or equal to 
75% of another phase 
for configured time 
setpoint
If set as ALARM: no 
phase is less than or 
equal to 75% of another;
If set as TRIP: RESET 
pressed or reset 
command received.
Overload trip There is a long or over-
temperature trip
RESET button is pressed 
or communications reset 
command received
Neutral current trip There is a neutral current 
trip
RESET button is pressed 
or communications reset 
command received
Short delay trip There is a short delay 
trip
RESET button is pressed 
or communications reset 
command received
Instantaneous trip There is an 
instantaneous trip or 
withstand (override) trip
RESET button is pressed 
or communications reset 
command received
Table 8.  Configurable relay functions (continued).
Condition/function 
name
Description of relay operation:
The relay will close 
when … 
The relay will open 
when … 
Short circuit trip There is a short, inst. or 
withstand (override) trip
RESET button is pressed 
or communications reset 
command received
Ground fault trip
(relay #2 default, GF 
styles)
There is a ground fault 
trip
RESET button is pressed 
or communications reset 
command received
Maintenance mode 
(ARMS) trip 
There is a maintenance 
mode trip
RESET button is pressed 
or communications reset 
command received
Any current protection 
trip 
(relay #3 factory default)
There is any type of 
protective current trip 
(overload, neutral, short 
delay, instantaneous, 
short circuit, ground 
fault, maintenance mode)
RESET button is pressed 
or communications reset 
command received
Mechanism trip There was a “sneaker” 
trip because the 
mechanism position 
switch indicates open 
but there is measurable 
current
RESET button is pressed 
or communications reset 
command received 
Open breaker pulsed An OPEN breaker 
command from any of 
the communications 
channels is received
Two seconds after the 
OPEN breaker command 
is received
Close breaker pulsed A CLOSE breaker 
command from any of 
the communications 
channels is received
Two seconds after the 
CLOSE breaker command 
is received
Remote control An output ON command 
for the relay specified 
in the command is 
received on any of 
the communications 
channels
An output OFF command 
for the relay specified 
in the command is 
received on any of 
the communications 
channels
4.2.1 Wiring and configuration for remote open/close
The on-board relays may be used to energize a shunt trip 
(ST) to open the circuit breaker or a spring release (SR) to 
close the circuit breaker when commanded via Modbus.  
Consult IL2C14762 & IL2C14761 for details on the shunt trip 
(ST) and spring release (SR) accessories.
To accomplish this requires three elements:
 •
Mapping the on-board relays to act using the open breaker 
pulsed or close breaker pulsed function;
 •
Wiring the on-board relays to an interposing relay to 
subsequently connect a power source to the ST/SR; and
 •
Programming a Modbus client to send the open breaker 
pulsed or close breaker pulsed commands.
To open the breaker, an on-board relay should be chosen and 
mapped to the open breaker pulsed function.  Do not map 
the same relay to any other functions or the ST will energize 
unexpectedly when that function causes the relay to close.  
The mapping can be accomplished using the display: Main 
menu -> Edit Settings -> Relay Config -> Open Command.