9. Modbus register map
POWER XPERT® RELEASE TRIP UNIT FOR MAGNUM PXR CIRCUIT BREAKERS MN013015EN January 2022 www.eaton.com
9.4.1 Group 0 – system group
Table 24. Modbus system group data (continued).
Func.
code
Register
number
Address
(hex)
Setpoint name R/W Definition
6 3000 0x0BB7 Password W factory default = 00000
3,4,6 3001 0x0BB8 Group 0 = system R/W 0x00FF selects group 0
3,4 3002 0x0BB9 Rating information R Values: 100, 200, 250, 300, 400, 500, 600, 630, 800, 1000,
1200, 1250, 1600, 2000, 2500, 3000, 3200, 4000, 5000, 6300
3,4 3003 0x0BBA Breaker frame R 0 = NRX NF
1 = NRX RF
2 = Magnum standard
3 = Magnum narrow
4 = Magnum double standard
5 = Magnum double narrow
3,4 3004 0x0BBB Style R 0 = PXR20VN30LNNC
1 = PXR20VN30LNNM
2 = PXR20VN30LGNC
3 = PXR20VN30LGNM
4 = PXR20VN30LGAC
5 = PXR20VN30LGAM
6 = PXR25VN30LNNM
7 = PXR25VN30LGNM
8 = PXR25VN30LNAM
9 = PXR25VN30LGAM
10 = PXR20VN30LNAM
11 = PXR20VN30LNAC
3,4,6 3006 0x0BBD Maintenance mode: Enable See
note
b08: MM current state (read only)
b07: MM rotary switch on/off (read only)
b06: MM rotary switch position valid or not (read only)
b01: MM remote control, 0=off, 1=on (read/write)
b00: MM local control (read only)
3,4,6 3007 0x0BBE Maintenance mode: Level R/W 0 = 1.5*I
n
1 = 2.5*I
n
2 = 4.0*I
n
3 = 6.0*I
n
4 = 8.0*I
n
5 = 10.0*I
n
3,4 3008 0x0BBF Frequency R 50, 60, or 400 Hz
3,4,6 3009 0x0BC0 Rev. feed R/W PXR 25 only
0 = forward
1 = reverse
3,4,6 3010 0x0BC1 Sign convention R/W PXR 25 only
0 = IEC
1 = IEEE
2 = IEEE alt
3,4,6 3011 0x0BC2 Demand window R/W PXR 25 only
0 = fixed
1 = sliding
3,4,6 3012 0x0BC3 Demand interval R/W PXR 25 only
5 to 60 (minutes)
3,4,6 3013 0x0BC4 Language R/W 0 = English
1 = Chinese
2 = German
3 = Spanish
4 = Portuguese
5 = French
.