2.1.5  Voltage transformers 
The installation may include a number of voltage 
transformers to measure the voltage on the cable side.  
Voltage transformers are fixed type. Each voltage 
transformer is fitted with 3 primary fuses. 
 
Cable side mounting:  
  Fixed in the cable compartment of a circuit breaker 
or contactor panel (to suit client requirements). 
  Voltage transformers can also be mounted in the 
bus-section or the riser panels as required. 
 
For special arrangements, a withdrawable busbar side 
voltage transformer truck can be provided. 
 
2.1.6  Current transformers 
Power Xpert
®
 UX switchgear can be equipped with 
current transformers for protection, measuring and 
metering. 
 
Current transformers are always fitted in the rear of the 
cable compartment or in the riser / sectionaliser panel.  
Standard version: 
  At the cable connection points for the feeder panels 
or supply panels. 
Customer-specific version: 
  In the riser or bus-section panel. 
 
2.1.7  Auxiliary equipment 
Auxiliary equipment such as relays, position indicators, 
meters and instruments are housed in the low-voltage 
compartment of each switch panel. 
 
Measuring and indicating equipment is fitted to the door 
of the low-voltage compartment. This also includes a 
circuit mimic diagram.  
 
Voltage Detection System 
The voltage indicator consists of three Light Emitting 
Diodes (LEDs) mounted in a small panel on the low-
voltage compartment of a switch panel. Each LED is 
connected to a measurement capacitor connected to a 
phase of the primary cable. The LEDs light up when the 
cable is live. This indicates that the cable is live without 
the use of a voltage transformer.